Installation Instructions (cont*d)

Temperature-Pressure Relief Valve

AWARNiNG

At the time of manufacture this water heater was provided
vnth a combination temperature-pressures reilef valve certified

by a nationally recognized testing laboratory that maintains
periodic inspection of production of listed equipment or mate­
rials, as meeting the requirements for Reiief Valves and

Automatic Gas Shutoff Devices for Hot Water Supply Systems,
and the latest edition of ANSI Z2I.22 and the code require­

ments of ASME. If replaced, the valve must meet the require­
ments of local codes, but not less than a combination tempera­

ture and pressure relief valve certified as meeting the require­
ments for Relief Valves and Automatic Gas Shutoff Devices for

Hot Water Supply Systems, ANSI Z2I.22 by a nationally recog­

nized testing laboratory that maintains periodic inspection of
production of listed equipment or materials.

The valve must be marioed mth a maximum set pressure not
to exceed the marked hydrostatic working pressure of the
water heater (ISO Ibsfsq. in.) and a discharge capacity not less
than the water heater input rate as shown on die model rating

plate. (Electric heaters - watts divided by 1000 x 3415 equal
BTU/Hr. rate.)

Your local jurisdictional authority, while mandating the use of a
temperature-pressure relief valve complying with ANSI Z2I.22
and ASME, may require a valve model different from the one
furnished vidth tiie water heater.
Compliance with such local requirements must be satisfied by

the installer or end user of the water heater with a locally pre­
scribed temperature-pressure relief valve installed In the desig­
nated opening in the water heater in place of the fectory for-

nished valve.

For safe operation of the water heater, the relief valve must not

be removed from it^ designated opening or plugged.

The temperature-pressure relief valve must be installed directly

into the fitting of the water heater designated for the relief valve.
Position the valve downward and provide tubing so tiiat any dis­

charge will exit only within 6 inches above, or at any distance

below the structural floor. Be certain that no contact is made

with any live electrical part The diKhatge opening must not be
blocked or reduced in size under any circumstances. Excessive
lengA, over 30 feet, or use of more than four elbows can cause
restriction and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the relief

vatrç and the tank. Do not connect tubing directly to discharge
drain unless a 6" air gap is provided. 1b prevent bodily injury, haz­

ard to life, or property damage, the relief valve must be allowed

to discharge water in quantities should circumstances demand. If
the dischai^ pipe is not connected to a dr^n or other suitable

means, the water flow may cause property damage.

The Discharge Pipe:

* Must not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

* Must not be plumed or blocked.
> Must be of material listed for hot water distribution.
■ Must be installed so as to allow complete drainage of both

the temperature-pressure relief valve, and the discharge
pipe.

■ Must terminate at an adequate drain.
* Must not have any valve between the relief valve and tank.

AWARNING

The temperature-pressure relief valve must be manually
operated at least once a year. Caution should be taken to
ensure that (I) no one b in front of or around the outlet of
the temperaiure-pressure reilef valve discharge line, and (2)
the water manually discharged will not cause any bodily
injury or property damage because the water may be
extremely hot

If after manually operating the valve, it feib to ccmipletely

reset and continues to reiràse water, immediately dose the
cold water inlet to the water heater, follow the draining
instructions, and replace the temperature-pressure relief

valve with a new one.

HOT

SHUTOFF COLD

VALVE

TEMPERATURE-

PRESSURE

REUEF VALVE

DISCHARGE PIPE

(Do not cap or plug)

i“AIR GAP

RELIEF VALVE OPENING

At the time of itnnufKture. this water heater was proved with a combination tem­

perature-pressure reiief valve listed as complying with the standard ^ i^lief vaim and

automatic gas shut-ofF devices for hot water supply systems. ANSI

^ safe

operaciofl of the water heater, the reiief vaive must not be removed from its designated
point of instaílatíon or plugged.

Your local jurisdictional authority, while mandating the use of a temperature-pressure

relief i^ve compl)nng with W'fSI Z2I.22 and ASME, may require a valve model different

from the one furnished with the water heater.

Comf^iance with such local requirements must be satisfied by the installer or end user

of the water heater with a locally prescribed temperature-pressure rdi^ valve installed
in the designated opening In the water heater.

See manual heading -"Temperature-Pressure Relief Wives" for installation and mainte­

nance of relief valve, discharge line, and other safety precautions.