Gas piping, A warning, Breathing hazard - cartoon monoxide gas – Kenmore Power Miser 12 153.331413 HA User Manual

Page 16: Fire and explosion hazard, Gas piping -16, Awarning, Warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases which couid cause deadly asphyxiation.

Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propeliants, cleaning solvents, refrigerator and air
conditioner

refrigerants,

swimming

pool

chemicals,

calcium

and sodium chloride, waxes, bleach and process chemicais
are typicai compounds which are potentially corrosive.

Gas Piping

V

AWARNING

Fire and Explosion Hazard

è

• Do not use water heater with

any gas other than the gas

shown onthe rating plate.

Excessive pressure to gas

control valve can cause serious
injury ordeath.

Turn off gas lines during

installation.

• Contact qualified installer or

service agency.

Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed

14 inch water column (3.5kPa) for natural and propane gas

(L.P.) gas. The minimum inlet gas pressure listed on the rating

plate is for the purpose of input adjustment, if the gas control

vaive is subjected to pressures exceeding 1/2 pound per square

inch (3.5kPa), the damage to the gas control valve could result

in a fire or explosion from leaking gas.

If the main gas line shutoff serving all gas appliances is used,
also turn “OFF” the gas at each appliance. Leave all gas

appliances shut “OFF" until the water heater installation is
complete.

A gas line of sufficient size must be run to the water heater.

Consult the current edition of National Fuel Gas Code ANSI
Z223.1/NFPA 54 and your gas supplier concerning pipe size.

A

WARNING

Breathing Hazard - Cartoon Monoxide Gas

High altitude orifice must be installed

for operation above 3,300 ft. (1,006 m)
or 5,500 ft. (1,676 m) for a high altitude

models.

Contact a qualified installer or service
agency.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

If a standard model is installed above 3,300 feet (1,006 m) or a

high altitude model is installed above 5,500 feet (1,676 m) the

input rating should be reduced at the rate of 4 percent for each
1,000 feet (305 m) above sea level which requires replacement

of the burner orifice in accordance with National Fuel Gas Code
ANSI Z223.1/NFPA 54. Contact your local Sears Service Center

or local gas supplier for further information.

Failure to replace the standard orifice with a high altitude orifice

when installed at elevations above 3,300 feet (1,006 m) or
above 5,500 feet (1,676 m) for high altitude model) could result

in improper and inefficient operation of the appliance, producing

carbon monoxide gas in excess of safe limits, which could

result in serious injury or death. Contact your local Sears Service

Center or local gas supplier for any specific changes which

may be required in your area.

A WARNING

Fire and Explosion Hazard

Use joint compound or tape

compatible with propane.

Leak

test

before

operating

heater.

Disconnect

gas

piping

and

shut-off valve before pressure
testing system.

There must be:

A readily accessible manual shut off valve in the gas supply

line serving the water heater, and

A drip leg (sediment trap) ahead of the gas control valve to

help prevent dirt and foreign materials from entering the

gas control vaive.

A flexible gas connector or a ground joint union between the

shut off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

The minimum inlet gas pressure shown on the rating plate is
that which will permit firing at the rated input.

Use pipe joint compound or teflon tape marked as being

resistant to the action of petroleum (Propane [L.P.]) gases.

The appliance and its gas connection must be leak tested

before placing the appliance in operation.

The

appiiance

and

its

individual

shutoff

valve

shall

be

disconnected from the gas supply piping system during any

pressure testing of that system at test pressures in excess of
1/2 pound per square inch (3.5kPa). It shall be isolated from

the gas supply piping system by closing its individual manual
shutoff valve during any pressure testing of the gas supply

piping system at test pressures equal to or less than 1/2 pound

per square inch (3.5kPa).

Connecting the gas piping to the gas control valve of the water

heater can be accomplished by either of the two methods

shown in Figures 19 and 20.

16

Advertising
This manual is related to the following products: