Sediment traps, Awarning, Fire and explosion hazard – Kenmore Power Miser 12 153.331413 HA User Manual

Page 17: Sediment trap -17

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Sediment Traps

AWARNING

Fire and Explosion Hazard

Contaminants in gas lines can
cause fire or explosion.

Clean

all

gas

piping

before

installation.

Install drip leg in accordance

with NFPA 54.

Contaminants in the gas lines may cause improper operation
of the gas control valve that may result in fire or explosion.

Before attaching the gas line be sure that all gas pipe is clean

on the inside. To trap any dirt or foreign material in the gas

supply line, a drip leg (sometimes called a sediment trap)
must be incorporated in the piping. The drip leg must be readily

accessible. Install in accordance with the

Gas Piping

section.

Refer to the current edition of the National Fuel Gas Code,
ANSIZ223.1/NFPA54.

A sediment trap shall be installed as close to the inlet of the
water heater as practical at the time of water heater installation.

The sediment trap shall be either a tee fitting with a capped

nipple in the bottom outlet or other device recognized as an
effective sediment trap. If a tee fitting is used, it shall be installed
in conformance with one of the methods of installation, shown

in Figures 19 and 20.

FIGURE 19. GAS PIPING WITH FLEXIBLE CONNECTOR

FIGURE 20. GAS PIPING WITH ALL

BLACK IRON PIPE TO GAS CONTROL

17

Advertising
This manual is related to the following products: