Connecting electric dryers (cont.), Connecting electric dryers, A warning – Kenmore ELITE 796.7927# User Manual

Page 13: Four-wire power cord, Three-wire power cord, Connecting gas dryers ,11, Connecting electric dryers ,13, Warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

INSTALLATION INSTRUCTIONS

CONNECTING ELECTRIC DRYERS (cont.)

CONNECTING ELECTRIC DRYERS

A

WARNING:

• Connect the power cord to the terminal block.

Each colored wire should be connected to same

color screw. Wire color Indicated on manual Is con­

nected to the same color screw In block. Failure to

follow these Instructions may result In a short or
overload.

Four-Wire Power Cord

'

A 4-wlre connection Is required for all mobile

and manufactured home Installations, as
well as all new construction after January 1,

1996.

A UL-listed strain relief is required.

Use a

30-amp, 240-volt, 4-wlre, UL-llsted power

cord with #10 AWG-mlnImum copper conductor

and closed loop or forked terminals with upturned
ends.

O Remove the terminal block access cover on the upper

back of the dryer.

0

Install a UL-listed strain relief into the power cord

through-hole.

©Thread a

30-amp, 240-volt, 4-wlre, UL-llsted power

cord with #10 AWG-mlnImum copper conductor

through the strain relief.

O Transfer the dryer’s white ground wire from behind the

green ground screw to the center screw of the termi­
nal block.

0

Attach the two hot leads of the power cord to the outer

terminal block screws.

0

Attach the white neutral wire to the center screw of
the terminal block.

O Attach the power cord ground wire to the green

ground screw.

O TIGHTEN ALL SCREWS SECURELY.

0

Reinstall the terminal block access cover.

Grounding through the neutral conductor Is pro­
hibited for: (1) new branch-circuit Installations, (2)
mobile homes, (3) recreational vehicles, and (4)
areas where local codes prohibit grounding
through the neutral conductor.

Three-Wire Power Cord

A 3-wlre connection Is NOT permitted on

new construction after January 1,1996.

' A UL-listed strain relief is required.

■ Use a

30-amp, 240-volt, 3-wlre, UL-llsted power cord

with #10 AWG-mlnImum copper conductor

and closed

loop or forked terminals with upturned ends.

(A
3

o

z

u

o

Remove the terminal block access cover on the upper

back of the dryer.

@ Install a UL-listed strain relief into the power cord

through-hole.

©Thread a

30-amp, 240-volt, 3-wlre, UL-llsted power

cord with #10 AWG-mlnImum copper conductor

through the strain relief.

O Attach the two hot leads of the power cord to the outer

terminal block screws.

0

Attach the neutral (center) wire to the center terminal
block screw.

0

Connect the external ground (if required by local
codes) to the green ground screw.

© TIGHTEN ALL SCREWS SECURELY.
O Reinstall the terminal block access cover.

13

Advertising
This manual is related to the following products: