4 power wiring, Figure 9, Figure 10 – Caterpillar TAURUS 70 User Manual

Page 24: Typical direct-drive ac start system

Advertising
background image

Turbomachinery Package Specification

Taurus

70 Compressor Set and Mechanical Drive

Figure 9. Typical Direct-Drive AC Starter Motor and Variable Frequency Drive


M

GAS

TURBINE

VARIABLE

FREQUENCY

DRIVE

RADIO

INTERFERENCE

FILTER

AC POWER

CONNECTION

CLUTCH

ASSEMBLY

AC

MOTOR

LINE REACTOR

Figure 10. Typical Direct-Drive AC Start System


7.2.4 Power

Wiring

The start system (Figure 10) requires customer-furnished, three-phase AC input.
Additional three-phase AC power wiring is required to connect the VFD to the starter
motor. A start contactor is not required for VFD operation. A customer-furnished fused
disconnect at the VFD input is recommended. Optional motor space heater wiring is
available.

Table 6.

Direct Drive AC Start System Specifications

Variable Frequency Drive

Optional Voltage Input Ranges

380 to 460 VAC, (48 to 62 Hz)

Minimum Input Current

- 380 to 460 VAC Input

105 amps

Voltage Output Range

0 to 460 VAC, (0 to 240 Hz)

Maximum Line Distribution Capacity

1000 kVa

Maximum Fault Current Capacity

30 000 amps, See Note (a)

Power Factor

0.96

Efficiency 98%