8 exterior connections, 9 fire and gas detection system, Figure 21 – Caterpillar TAURUS 70 User Manual

Page 50: Typical fire and gas system, Turbomachinery package, Figure 21. typical fire and gas system

Advertising
background image

Turbomachinery Package Specification

Taurus

70 Compressor Set and Mechanical Drive

The intent of the enclosure design is to comply with U.S. Occupational Safety and Health
Administration (OSHA) standards for eight-hour employee exposure. Transmission loss
of the panels in decibels is available upon request. Further information is available in
Solar’s publication SPNP, “Noise Prediction Guidelines for Industrial Gas Turbines.”

12.2.8 Exterior

Connections

Connections for oil vent line, fire and gas suppression systems, and gas turbine air inlet
and exhaust are terminated outside the enclosure.

12.2.9 Fire and Gas Detection System

Enclosed packages must include a fire and gas control system. The fire and gas system
supplied by Solar (Figure 21) provides gas monitoring, fire detection, and extinguishing
agent release using an advanced distributed architecture to monitor gas, heat, and
optical flame detectors. The system communicates with the Turbotronic 4 control system
to initiate a shutdown if a fire or a high gas level is detected. On the package exterior,
indicator lights, strobe lights, and an alarm horn provide system status. A keyswitch is
provided to inhibit the system and a push button switch is provided to manually release
the fire-extinguishing agent.
The primary fire detection system uses multi-spectrum infrared (MIR) flame detectors.
The system includes an automatic optical integrity feature to provide a continuous check
of the optical surfaces, detector sensitivity, electronic circuitry of the detector-controller
system, and automatic fault identification with digital display of system status in numerical
code. The secondary detection system consists of rate-compensated thermal detectors.
The two detection systems act independently in detecting and reporting a fire.

OPERATOR PANEL

EQP

DCIO

MIR

MIR

MIR

MIR

IR

IR

TD

TD

TD

TD

Turbotronic

4

Control

Processor

Turbotronic

4

Back-up

Shutdown

System

Turbomachinery Package

To / From Customer
Supervisory System

STROBES / HORN

FIRE

SUPPRESSION

SYSTEM

AUTO

INHIBIT

DISCHARGED

AUTO / INHIBIT

MANUAL RELEASE

LON

DCIO

MIR =

Multi-spectrum IR Flame Detector

TD

=

Thermal Detector

IR

=

IR Gas Detector

LON =

Local Operating Network

ControlNet

Figure 21. Typical Fire and Gas System

© 2009 Solar Turbines Incorporated. All rights reserved.

TPS70CSMD/309