Interlogix TruPortal User Manual

Page 66

Advertising
background image

Configuring the System

54

TruPortal Software User Guide

Note the following details about triggers:

Up to ten groups of condition statements can be created, with up to ten condition statements
across all groups (for example, two groups could have five conditions each).

To start a new group of condition statements, click the [+] button that appears above the
condition statements in an existing group. Click the [-] button to remove a group of condition
statements.

A second level of [+] and [-] buttons appears next to each individual condition statement. Click
the [+] button to add a new condition statement; click the [-] button to remove a single condition
statement.

For either one specific group of condition statements or for all groups of condition statements,
Any Can Occur or All Must Occur can be selected.

If Any or All is selected as the qualifier for an entity in a condition statement, any new objects
added to the System of the same entity type are automatically included in the condition
evaluation. For example, if condition statement is created to monitor all readers and a new reader
is installed, the new reader is added to the group of readers being monitored automatically.

The trigger conditions for readers will always trigger false immediately after triggering true.
Also, deactivation actions are not typically used with reader trigger conditions.

15 Minutes Before Start

Becomes true when 15 minutes prior to schedule start.
Becomes false when schedule starts.

15 Minutes Before End

Becomes true when 15 minutes prior to schedule end.
Becomes false when schedule ends.

Entity: System

Lockout All Doors -
Command

Becomes true when lockout goes active. Becomes false
when lockout is no longer active.

Unlock All Doors -
Command

Becomes true when unlock goes active. Becomes false
when unlock is no longer active.

Trouble

Becomes true when External/Wall Tamper goes active.
Becomes false when tamper condition goes inactive.

Backup Battery Low

Becomes true when battery voltage drops below 11.7
VDC. Becomes false when battery voltage goes above
11.7 VDC.

Memory Battery Low

Becomes true when battery voltage drops below 2.0
VDC. Becomes false when battery voltage goes above
2.0 VDC. Only checked every 6 hours.

AC Power Failed

Becomes true when AC power is removed. Becomes
false when AC power is restored.

Fuse Tripped

Becomes true when any fuse trips. Becomes false when
all fuses are restored.

Time Changed

Becomes true when time is changed. Will not rearm for
one minute. Automatically becomes false after one
minute.

Trigger conditions

Notes