Crestron electronic DIN Rail Control Processor DIN-AP2 User Manual

Page 12

Advertising
background image

DIN Rail Control Processor

Crestron DIN-AP2

Connectors, Controls & Indicators

# CONNECTORS

1

,

CONTROLS &

INDICATORS

DESCRIPTION

1

I/O VERSIPORTS 1-8

(1) 9-pin 3.5mm detachable
terminal block comprising (8)
digital input/output or analog
input ports (referenced to GND)

Max Wire Size: 1.5 mm

2

(16 AWG)

Digital Input:

Rated for 0-24 Volts DC

Input Impedance 20k ohms

Logic Threshold: 1.25 Volts

DC

Analog Input:

Rated for 0-10 Volts DC,

protected to 24 Volts DC
maximum

Input Impedance 20k ohms

Digital Output:

250 mA sink from maximum

24 Volts DC, catch diodes
for use with “real world”
loads

Programmable 5 Volts, 2k ohms
pull-up resistor per input

2

PWR LED

(1) Green LED, indicates power
supplied to unit via NET port

3

NET LED

(1) Yellow LED, indicates
Cresnet bus activity

(Continued on following page)