LDVT Series Direct Vent GaS Fireplace

10007852

Installation:
1. Thread the wiring through holes on the end panels

of appliance. Take care not to cut wire or insulation
on metal edges. Route the wire to a conveniently
located receptacle box.

2. Attach the wire to the ON/OFF switch and install the

switch into the receptacle box.

3. Connect the other ends of the wire to the gas control

valve. (Fig. 6)

When purging gas line, the front window
frame removed.

The gas pipeline can be brought in through the rear
of the fireplace as well as the bottom. Knockouts are
provided on the bottom behind the valve to allow for the
gas pipe installation and testing of any gas connection.
It is most convenient to bring the gas line in from the
rear right side of the valve as this allows fan installation
or removal without disconnecting the gas line.

The gas line connection can be made with properly
tinned 3/8” copper tubing, 3/8” rigid pipe or an approved
flex connector. Since some municipalities have ad-
ditional local codes, it is always best to con- sult your
local authority and the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 in the USA or the CSA-B149.1 installa-
tion codes.

Do not wire the remote ON/OFF wall switch
for the gas fireplace to the 120 volt power
supply.

Always check for gas leaks with a mild
soap and water solution. Do not use an
open flame for leak testing.

The gas control is equipped with a captured screw type
pressure test point, therefore it is not necessary to pro-
vide a 1/8” test point up stream of the control.
When using copper or flex connector use only approved
fittings. Always provide a union when using black iron
pipe so that the gas line can be easily disconnected for
burner or fan servicing . See gas specifications for pres-
sure details and ratings.

Gas Line Installation

Remote ON/OFF Switch

Alternate Switch Location

The remote switch can be installed on the front/side of

the access door. Simply mount the switch to the bracket

provided and screw the bracket to either side of the

frame, lining up the screws with the pre-punched holes.

(Fig. 7)

FP297A

INSTA VENT FREE

UVHB26 GAS SUPPLY

7/1/98

FP297A

1/2” Gas Supply

1/2” NPT X 1/2” Flare Shut-off Valve

3/8” Flex line
(from valve)

Fig. 5 Typical gas supply installation.

FP1024

alternate

remote switch

location

1/27/00 djt

FP1024

Fig. 7 Alternate switch location.

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the cur-
rent ANSI Z223.1/NFPA 54 and/or local codes hav-
ing jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).

Remote ON/OFF

Switch or Thermostat or

Remote Control

Gas
Control
Valve

FP1224

Fig. 6 Remote switch wiring diagram.

TP

TH

TP

TH

FP1224

Remote switch

11/02

The fireplace valve must not be subjected to any test
pressures exceeding 1/2 psi. Isolate or disconnect this
or any other gas appliance control from the gas line
when pressure testing.