LAARS Mighty Therm2 MT2V (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 20

Advertising
background image

LAARS Heating Systems

Page 20

SECTION 4B.

Water Connections —

Mighty Therm2 Water Heater

4B.1 Water System Piping —

Water Heater

Hot water piping should be supported by suitable

hangers or floor stands. Do not support piping with

this appliance. Due to expansion and contraction of

copper pipe, consideration should be given to the type

of hangers used. Rigid hangers may transmit noise

through the system resulting from the piping sliding in

the hangers. It is recommended that padding be used

when rigid hangers are installed.

The Mighty Therm2 can be used with several

different types of readily available storage tanks. A

pump draws water from the storage tank and pumps

the water through the heater and back into the tank.

Pump-mounted units have a circulating pump built

into the water heater. The pumps used are sized for

the head loss through the heater, plus 30 feet (9.1 m)

of full-sized piping (same size as boiler outlet) and

a normal number of fittings. Pumps used on pump-

mounted unit are sized for soft/normal or hard water,

so make sure a pump-mounted unit matches the water

quality of the installation.

Pipe the outlet from the heater’s relief valve

such that any discharge from the relief valve will be

conducted to a suitable place for disposal when relief

occurs. Do not reduce line size or install any valves in

this line. The line must be installed to allow complete

drainage of both the valve and the line.

Suggested piping diagrams are shown in

Figures

9, 10, 11 and 12.

These diagrams are meant only as a

guide. Components required by local codes must be

properly installed.

Note the recommended location of the

temperature sensor on the diagrams. The Mighty

Therm2 is shipped with an additional sensor that can

be used for more full-featured domestic water heating

control. To get these features, you must provide a

location for the additional sensor. It can be strapped to

a pipe from 1" to 4" diameter, or inserted into a tank

immersion well.

The minimum inlet water temperature for the

Mighty Therm2 is 120°F (49°C) to avoid condensing

on the copper coils.

4B.2 Hot Water Supply Piping —

Water Heater

Follow the tank manufacturer’s guidelines for

completion of the hot water system connections.

NOTE: A listed temperature and pressure relief

valve listed as complying with the Standard

for Relief Valves and Automatic Gas Shutoff

Devices for Hot Water Supply Systems (ANSI

Z21.22/CSA 4.4), of suitable discharge capacity

must be installed in the separate storage tank

system.

If the Mighty Therm2 water heater is installed

in a closed water supply system, such as one having a

backflow preventer in the cold water supply line, the

relief valve may discharge periodically, due to thermal

expansion. Means (such as a properly-sized expansion

tank) shall be provided to control thermal expansion.

Contact the water supplier or local plumbing inspector

on how to control this situation.

4B.3 Water Flow Requirements —

Water Heater

In a water heating application (an open system),

new water is constantly being introduced. With the

new water comes a fresh supply of minerals that can

be deposited on the unit’s heat exchanger. This is

commonly known as scaling. The amount of minerals

will depend upon the hardness of the water. Water can

also be aggressive, and can erode metals, including

copper, if the water is moved too quickly. The water

flow requirements for the Mighty Therm2 water heater

are based upon the hardness of the water. The water

flow is kept high enough to prevent scaling, but low

enough to prevent tube erosion. For extremely soft or

hard water, cupro-nickel tubes are available. Contact a

Laars representative if you have questions or concerns

about water quality.

Pump-mounted water heaters can be ordered with

standard pumps for soft or normal water. The pumps

used are sized for the head loss through the heater, plus

30 feet (9.1m) of full-sized piping (same size as heater

outlet) and a normal number of fittings. For hard water

conditions (more than 17 grains per gallon), use a

non-pump-mounted heater with a properly-sized field-

installed pump.

Table 9

specifies water flow rates for water

heaters, which will enable the user to size a pump. The

head loss shown is for the heater only, and the user

will need to add the head loss of the piping system to

properly size the pump.

4B.4 Combined Water Heating (potable)

and Space Heating — Water Heater

NOTE: These systems are not allowed in the

Commonwealth of Massachusetts.

Piping and components connected to this water

heater for the space heating application shall be

suitable for use with potable water.

Toxic chemicals, such as used for boiler

treatment, shall not be introduced into the potable

water used for space heating.

This water heater when used to supply potable

water shall not be connected to any heating system

or component(s) previously used with a non-potable

water heating appliance.

Advertising
This manual is related to the following products: