2 model identification, 3 warranty, 4 dimensions – LAARS Mighty Therm2 MT2V (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 4: 5 locating the appliance

Advertising
background image

LAARS Heating Systems

Page 4

1.2 Model Identification

Consult the rating plate on the unit. The

following information describes the model number

structure.

Model Character Designation

1-3 Model Series Designation

M T 2 = Mighty Therm2

4 Usage

H = Hydronic

V = Volume Water

5-8 Size

0 2 0 0 = 199,900 BTU/h input

0 3 0 0 = 300,000 BTU/h input

0 4 0 0 = 399,900 BTU/h input

9 Fuel

N = Natural Gas

P = Propane

10 Altitude

A = 0-10,000 feet

11 Location

C = Indoor and Outdoor

12 Firing Mode

C = On-Off (standard)

K = Two-stage (optional)

13 Revision

2 = Revision Level 2

14 Heat Exchanger

B = Glass-lined CI / copper / brz trim (std. MT2V)

C = Glass-lined cast iron / copper (std. MT2H)

N = Glass-lined cast iron / cu-nickel

P = Glass-lined cast iron / cu-nickel / brz trim

2 = Glass-lined cast iron / copper, brz trim, HLW

5 = Glass-lined cast iron / cu-nickel / brz, HLW

15 Options Code

X = Standard unit

L = Low temperature control (std. MT2V)

16 Pump Options

X = No Pump

N = Pump mounted, normal water, Taco

S = Pump mounted, soft water pump (MT2V

only), Taco

G = Pump mounted, normal water, Grundfos

1.3 Warranty

Laars Heating Systems’ Mighty Therm2

appliances are covered by a limited warranty. The

owner should fill out the warranty registration card and

return it to Laars Heating Systems.

All warranty claims must be made to an

authorized Laars Heating Systems representative or

directly to the factory. Claims must include the serial

number and model (this information can be found

on the rating plate), installation date, and name of

the installer. Shipping costs are not included in the

warranty coverage.

Some accessory items are shipped in separate

packages. Verify receipt of all packages listed on

the packing slip. Inspect everything for damage

immediately upon delivery, and advise the carrier of

any shortages or damage. Any such claims should be

filed with the carrier. The carrier, not the shipper, is

responsible for shortages and damage to the shipment

whether visible or concealed.

1.4 Dimensions

See Figures 1A and 1B.

1.5 Locating the Appliance

The appliance should be located to provide

clearances on all sides for maintenance and inspection.

It should not be located in an area where leakage of

any connections will result in damage to the area

adjacent to the appliance or to lower floors of the

structure.

When such a location is not available, it is

recommended that a suitable drain pan, adequately

drained, be installed under the appliance.

The appliance is design certified by CSA-

International for installation on combustible flooring;

in basements; in closets, utility rooms or alcoves.

Mighty Therm2 Boilers or Water Heaters must

never be installed on carpeting. The location for the

appliance should be chosen with regard to the vent

pipe lengths and external plumbing. The unit shall be

installed such that the gas ignition system components

are protected from water (dripping, spraying, rain, etc.)

during operation and service (circulator replacement,

1 2 3

4 5 6 7 8 9

10

11

12

13

14

15

16

M T 2

A

C

2

SERIES

M T 2

USAGE

H
V

SIZE

0 2 0 0

0 3 0 0

0 4 0 0

FUEL

N
P

ALTITUDE

A

FIRING

MODE

C
K

LOCATION

C

REVISION

2

HEAT

EXCHANGER

B
C
N
P

2
5

OPTIONS

CODE

X
L

PUMP

OPTIONS

X
N
S

G

Advertising
This manual is related to the following products: