LAARS Mighty Therm2 MT2V (Sizes 200, 300, 400) - Install and Operating Manual User Manual

Page 27

Advertising
background image

Mighty Therm

2

(200, 300, 400)

Page 27

LEDs State Description

1. Power

2. Heat – On = call for heat; Flashes for Boiler

sensor error

3. DHW – On = call for DHW; Flashes for

outdoor sensor error

4. WWSD – On = Outdoor Reset AND WWSD

Active AND control in WWSD; Flashes for outdoor

sensor error, operation continues with fixed boiler

target of 140°F.

When a call for HEAT and/or DHW is present

the pump contact (5A max) will be energized. Post

purge can be selected via dip switch #5, Pump Post

Purge Inactive (Off) /Active 3 min. (On). In the On

position the pump will continue to run for 3 min after

the last call has been satisfied. When the dip switch is

Off there is no post purge of the pump, the pump turns

off immediately after the last call is removed. Laars

strongly recommends using a pump post purge. During

WWSD and a call for HEAT is present the pump will

remain off.

Pump Exercising The control exercises the

boiler pump every 3 days of inactivity. While the

control is exercising the pump all LEDs will turn off

and the power LED will flash for 10 seconds.

Staging (where applicable – factory setting):

Dip switch #1 is used to select the number of stages:

2-Stage (Off) / Single Stage (On).

For 2-stage operation, the first stage is cycled

on Proportional error and the second stage is cycled

based on PI according to a fixed algorithm. No user

adjustment is necessary.

Note: All stages are turned off when the water

outlet temperature reaches the Maximum setting

that is elected via dip switch #4, Boiler Maximum

210°F (Off) / 190°F (On). Commercial boilers have

dip switch #2 set for ‘Off’ to allow setpoint control.

Utilize dial to set desired outlet temp.

NOTE:

This boiler is equipped with a feature that saves

energy by reducing the boiler water temperature as

the heating load decreases. This feature is equipped

with an override which is provided primarily to permit

the use of an external energy management system

that serves the same function. THIS OVERRIDE

MUST NOT BE USED UNLESS AT LEAST ONE OF

THE FOLLOWING CONDITIONS IS TRUE:

• An external energy management system is

installed that reduces the boiler water temperature

as the heating load decreases.

• This boiler is not used for any space heating.

• This boiler is part of a modular or multiple boiler

system having a total input of 300,000 BTU/hr or

greater.

• This boiler equipped with a tankless coil.

Auto Boiler Target Setpoint: Space Heating:

The boiler target temperature is automatically

determined from Space Heating and DHW

requirements. Space heating is based on outdoor reset.

When both a Heat Call and a DHW Call are present

at the same time, the control operates to provide the

higher boiler target temperature.

Heating Curve (Outdoor Temperature Reset)

The control uses a linear heating curve to calculate

a target setpoint. The following data are used

to calculate the target setpoint from the outdoor

temperature.

1. The heating curve or reset ratio (RR) is set by

the potentiometer with a range of 0.4 to 3.6.

2. The room temperature is fixed at 70 deg F.

3. Boiler target = 70 deg F + RR x (70 deg F -

outdoor temp)

Outdoor

Heating Curve=Reset Ratio (RR)=

Temp F

1.0

2.0

3.0

Boiler Target F

-30

170

210

210

-20

160

-10

150

0

140

10

130

190

20

130

170

30

150

190

40

130

160

50

130

60

70

WWSD OFF

Boiler Target Temperature Calculation:

Boiler Target = 70 deg F +RR x (70–Outdoor

Temp)

DHW Operation The boiler target for DHW

calls is fixed at 180 deg F.

Note: There is no control of a DHW pump, so the

boiler pump runs with the call for DHW.

Limiting The boiler target is limited to a

minimum and a maximum target to ensure that the

water temperature does not exceed the limits.

1. Target Min - The boiler target minimum is

the point at which the stages will start to turn on to

maintain a minimum water temperature. The Boiler

Minimum water temperature is 130 deg F, regardless

of other calculated targets. To ensure that the water

temperature is greater than the Boiler Minimum water

temperature the target is increased to allow the stages

to cycle on by the Boiler Minimum water temperature,

Boiler Minimum target is set to Boiler Minimum +

Advertising