9.1.2 Economizer

Options

FIGURE 29 -

Component Locations

of Economizer Air

Control Options

AR2E and AR2F

Legend (applies to Option AR2E and AR2F):

NOTE: Damper linkage

may not provide

adequate air balance

of return and outside

air quantities. Compare

return duct and outside

air inlet hood pressure

drops to determine

balancing requirements.

Operating Sequence

with Economizer

Option AR2E

Option AR2F - Dry Bulb Econ-

omizer Control provides free

cooling for dry climates.

(

10) Barometric Relief Dampers

(

12) Outside Air Enthalpy Sen-

sor, Option AR2E

Outside Air Dry Bulb Sensor,

Option AR2F

(

2) Horizontal Air Intake and Exhaust Air

Openings

(

3) Bottom Return Air Opening

(

4) Outside Air Intake Dampers

(

5) Return Air Dampers

(

6) Modulating Damper Motor

(

9) Economizer Controls

Option AR2E - Reference Enthalpy Con-

trol provides free cooling with variable

building loads for temperate climates.

On a call for low stage cooling
1. The blower motor is energized.

2. With the outdoor enthalpy less than the return air enthalpy:

a) The "A" and "B" cool circuits are locked out.

b) Dampers are positioned by the economizer and mixed air sensor.

3. With outdoor air enthalpy higher than the return air enthalpy:

a) The "A" cool circuit is energized.

b) Dampers are positioned for minimum outside air.

c) On a call for high stage cooling, the "B" circuit is staged appropriately.

FX05/FX06 Controller

Setting Change

Display New Default
EN1

20

29

OC1

58°F 68°F

With the economizer and return air, the "mixed" air temperature sensed at the

evaporator coil is raised. Lowering the EN1 and OC1 setpoints on the control-

ler as shown in the table, will allow the enthalpy controller on the economizer to

take over control of mechanical cooling. For instructions on setting the control-

ler, refer to the control instruction sheet in the literature envelope.
Also, check the enthalpy setting on the economizer; it needs to be at the

"D" setting. Adjust the minimum position potentiometer for the mixture of air

required for the installation.
(NOTE: The EXH, DCV1, and CDV2 functions on the control are not used.)

9.1.3 Energy

Recovery Module

Options

Energy recovery modules are shipped separately for field installation. Modules

include an enthalpy wheel, a supply air blower, an exhaust blower, an intake

hood, and an exhaust hood with a gravity damper. Energy recovery modules

are identified as Option ER and are selected by CFM. The modules also have a

variety of options. In addition to the Option ER energy recovery module, either

air control Option AR2B or AR2A is required. See

FIGURE 30A or FIGURE

30B for application and control components.
Follow the installation instructions shipped with the module.