WARNING: PRESSURE TESTING SUPPLY PIPING

Test pressures ABOVE 1/2 psi (3.5kPa): Disconnect the heater and the

manual valve from the gas supply line which is to be tested. Cap or plug the

supply line.

Test pressure EQUAL TO or BELOW 1/2 psi (3.5kPa): Before testing, close
the manual valve at the heater.

Furnaces for natural gas are orificed for operating with gas having a heating

value of 1000 (±50) BTU per cubic ft. If the gas at the installation does not meet

this specification, consult the factory for proper orifice.
Pipe joint compounds (pipe dope) shall be resistant to the action of liquefied

petroleum gas or any other chemical constituents of the gas being supplied.

WARNING: All components of a gas supply system must be

leak tested prior to placing equipment in service. NEVER

TEST FOR LEAKS WITH AN OPEN FLAME. Failure to comply

could result in personal injury, property damage or death.

FIGURE 32 - Gas

Connection

���������

����������

����

���

������

�������

������

������

����

Gas Connection Size

Heat Section Gas

Connection
100 - 300

1/2"

350 - 400

3/4"

450 - 700

1"

Sizing Gas Supply

Lines

CAPACITY OF PIPING - Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)

Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)

Length

Diameter of Pipe

of

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

2-1/2"

Pipe

Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane

20 ft

92

56

190

116

350

214

730

445

1100

671

2100

1281

3300

2013

30 ft

73

45

152

93

285

174

590

360

890

543

1650

1007

2700

1647

40 ft

63

38

130

79

245

149

500

305

760

464

1450

885

2300

1403

50 ft

56

34

115

70

215

131

440

268

670

409

1270

775

2000

1220

60 ft

50

31

105

64

195

119

400

244

610

372

1105

674

1850

1129

70 ft

46

28

96

59

180

110

370

226

560

342

1050

641

1700

1037

80 ft

43

26

90

55

170

104

350

214

530

323

990

604

1600

976

90 ft

40

24

84

51

160

98

320

195

490

299

930

567

1500

915

100 ft

38

23

79

48

150

92

305

186

460

281

870

531

1400

854

125 ft

34

21

72

44

130

79

275

168

410

250

780

476

1250

763

150 ft

31

19

64

39

120

73

250

153

380

232

710

433

1130

689

175 ft

28

17

59

36

110

67

225

137

350

214

650

397

1050

641

200 ft

26

16

55

34

100

61

210

128

320

195

610

372

980

598

Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.

Refer to National Fuel Gas Code for additional information on line sizing.

Temperature

Guidelines for Gas

Heat Section

All piping must be in accordance with requirements outlined in the National Fuel

Gas Code ANSI/Z223.1a (latest edition) or CSA-B149.1 and B149.2. Gas sup-

ply piping installation should conform with good practice and with local codes.

9.3.2 Gas Heat

Module - Mechanical

9.3.2.1 Gas Piping and Pressures

Minimum Circulating Discharge

Air Temperature (°F)

80

75

70

65

60

Minimum Design Ambient (°F)

-30 to - 21 -20 to - 11 -10 to -1 0 to 9 10 and above

9. Optional Equipment including Heat Sections (cont'd)

9.3 Gas Heat Module - Models RDCA and RDDA (cont'd)

NOTE: If a Model

JHUP-0250 duct

furnace curb

section is part of the

installation, much of

the information in this

section applies to the

duct furnace also;

see Paragraph 9.4.