Ignition System

Fault Modes

sure switch recognition delay, the circuit board will respond to the loss of flame.

If the pressure switch remains open for 2 seconds and the flame remains, the

circuit board de-energizes the gas valve and the venter motor runs through

postpurge
Undesired Flame - If flame is sensed longer than 20 seconds while the gas

valve is de-energized, the circuit board shall energize the venter motor. When

flame is no longer sensed, the venter motor will run through postpurge. The

circuit board will do a soft lockout, but will still respond to open limit and flame.

The FLAME (yellow) LED shall flash rapidly when lockout is due to undesired

flame.

Gas Valve Relay Fault - If the circuit board senses the gas valve as energized

for more than one second when the circuit board is not attempting to energize

the gas valve, or the gas valve is sensed as not energized when it is supposed

to be energized, then the circuit board will lockout with the green LED off. The

control assumes either the contacts of the relay driving the gas valve have

welded shut, or the sensing circuit has failed. The venter motor is forced off to

open the pressure switch to stop gas flow unless flame is present.

If the gas valve was sensed as closed when it should be open, and has not de-

energized after the venter motor was shutoff for 15 seconds, then the venter

motor is re-energized to vent the unburned gas.

Soft Lockout - The circuit board shall not initiate a call for heat while in lock-

out. The circuit board will still respond to an open limit and undesired flame.

Lockout shall automatically reset after one hour. Lockout may be manually

reset by removing power from the circuit board for more than one second or

removing the call for heat for more than one and less than 20 seconds.

Hard Lockout - If the circuit board detects a fault on the board, the status LED

will be de-energized, and the circuit board will lockout as long as the fault

remains. A hard lockout will automatically reset if the hardware fault clears.

Power Interruption - During a momentary power interruption or at voltage

levels below the minimum operating voltage (line voltage or low voltage) the

ignition system will self-recover without lockout when voltage returns to the

operating range.
Power interruptions of less than 80mS shall not cause the circuit board to

change operating states. Power interruptions greater than 80mS may cause

the circuit board to interrupt the current operating cycle and re-start.

9.3.4 Venting and

Combustion Air
Location of the Vent

and Combustion Air

Inlets
FIGURE 39 -

Location of Flue

Exhaust (vent) and

Combustion Air

Openings

��������

�����������

������

��������������

��������������������

�������������������

��������������������

The gas heat section is power

vented. Presence of

combustion air pres-

sure is monitored by a

combustion air proving

switch.

The combustion air and flue

gas openings are carefully

designed screened openings

located on the side of the unit.

Position the system so that the flue dis-

charge is not directed at any fresh air

inlet.

9.3 Gas Heat Module - Models RDCA and RDDA (cont'd)

9. Optional

Equipment

including

Heat Sections

(cont'd)

9.3.3 Ignition System (cont'd)