Combustion Air

Proving Switch

The combustion air proving switch is a pressure switch that monitors air pres-

sure to ensure that proper combustion airflow is available. The switch on a

Size 100 furnace is designed to close when a negative pressure is sensed in

the venter housing. The switch on Sizes 150-700 senses the differential pres-

sure between the negative pressure in the venter housing and the pressure

in the cabinet. For location of the combustion air proving switch, see

FIGURE

20, page 33, Item 17.

Vent Extension Field

Kit

The gas-fired heat section vents combustion gas horizontally. A field-installed

vent extension kit (

P/N 221120) provides for attaching a vertical vent pipe that

will allow the vent terminal to extend above the unit. For information, contact

your distributor or see Form CP-MAPS-Vnt Ext on www.RezSpec.com.

Sensing Type

Size

Startup

(Cold)

Equilibrium

(Hot)

Setpoint ON

Setpoint

OFF

Label

Color

Switch

P/N

Single Negative

Pressure

100

1.2±.2" w.c.

0.65±.1" w.c.

0.68±.1" w.c.

0.5" w.c.

Orange

196388

Differential

Pressure

150

1.4±.2" w.c.

0.6±.1" w.c.

0.68±.1" w.c.

0.5" w.c.

Orange

196388

200

1.4±.2" w.c.

0.6±.1" w.c.

0.73±.1" w.c.

0.5" w.c.

White

196362

250

1.5±.2" w.c.

0.7±.1" w.c.

0.73±.1" w.c.

0.55" w.c.

White

196362

300

1.5±.2" w.c.

0.7±.1" w.c.

0.73±.1" w.c.

0.55" w.c.

White

196362

350

3.5±.2" w.c.

1.8±.2" w.c.

0.83±.1" w.c.

0.65"w.c.

Yellow

197028

400

3.3±.2" w.c.

2.0±.2" w.c.

0.83±.1" w.c.

0.65"w.c.

Yellow

197028

450

2.7±.2" w.c.

1.8±.2" w.c.

0.83±.1" w.c.

0.65"w.c.

Yellow

197028

500

2.8±.2" w.c.

1.8±.2" w.c.

0.83±.1" w.c.

0.65"w.c.

Yellow

197028

550

3.0±.2" w.c.

2.1±.2" w.c.

0.83±.1" w.c.

0.65"w.c.

Yellow

197028

600

3.0±.2" w.c.

2.1±.2" w.c.

0.83±.1" w.c.

0.65"w.c.

Yellow

197028

650

3.0±.2" w.c.

1.9±.2" w.c.

0.83±.1" w.c.

0.65"w.c.

Yellow

197028

700

3.0±.2" w.c.

2.0±.2" w.c.

0.83±.1" w.c.

0.65"w.c.

Yellow

197028

On startup when the furnace is cold, the sensing pressure is at the most nega-

tive level, and as the furnace and the flue system warmup, the sensing pressure

becomes less negative. After the system has reached equilibrium (approxi-

mately 20 minutes), the sensing pressure levels off. If a restriction causes the

sensing pressure to become less than the switch setpoint, the pressure switch

will function to shut off the burner. The burner will remain off until the system

has cooled and/or the flue system resistance is reduced. The table below gives

approximate water column negative pressure readings and switch setpoints for

sea level operating conditions.

DANGER: Safe

operation requires

proper venting

flow. Never bypass

the combustion air

proving switch or

attempt to operate

the unit without

the venter running

and proper flow in

the vent system.

Hazardous condi-

tion could result.

See Hazard Levels,

page 2.

9.3.5 High

Temperature Limit

Control

All furnaces are equipped with a temperature activated auto reset limit control.

The control is factory set and is non-adjustable. If the setpoint is reached,

the limit control will interrupt the electric supply to the gas valves. This safety

device provides protection in the case of a lack of airflow due to dirty filters or

a restriction at the inlet or outlet.
The limit control switch is mounted on the side of the heat exchanger with

a capillary sensor that extends across the discharge opening. The switch is

accessible in the blower compartment.

CAUTION: The auto reset limit control will continue to shut down

the heater until the cause is corrected. Never bypass the limit

control; hazardous conditions could result. See Hazard Intensity

Levels, page 2.