3 zone outputs, 3 zone outputs -6, 3). fo – SilentKnight 5700 User Manual

Page 104: N 7.3.1.3

Advertising
background image

Programming

151295

7-6

Heat Temperature Setting

Use this feature to set the temperature at which high temperature detectors will respond. All detectors in the zone
will respond in the same way. The range for the SD505-AHS heat detector is from 135°F to 150°F. The range for
SK-Heat-HT heat detector is from 135°F to 190°F.

The SD505-AHS and SK-Heat-HT heat detectors are absolute temperature devices. This means that they respond
to an alarm immediately if the temperature in the zone goes above the programmed temperature.

5.

Enter the temperature at which the heat detector will respond.

Or

Use the

or

keys to scroll through the range.

6.

Then press

ENTER

.

7.3.1.3 Zone Outputs

Output groups and cadence patterns are mapped to events. They can be programmed to output when an event
occurs in a zone. Some system trouble events can be mapped for the entire system. Section 6.2 of this manual
contains a general explanation of mapping. The following sections explain how to select mapping options.

Note: Use of multiple notification groups may not synchronize with each other.

Mapping to Zone Events

Eleven types of events can occur in zones. For each event type, you can activate up to 8 output groups or output
group templates, specifying a pattern for each.

Event types are:

Manual Pull Alarm (MP)

Water Flow Alarm (WF)

Detector Alarm (DE) (heat or smoke detectors)

Aux 1 and Aux 2 Alarm (A1 or A2) User-specified alarm types.

Pre-alarm (PR)

Supervisory (SU)

Trouble (TR)

Status Point (SP)

CO Alarm (CO)

CO Supervisory (SCO)

To map zone events to outputs, follow these steps:

1.

From the Main Menu, select 7 for Program Menu.

2.

From the Program Menu, select 2 for Zone.

3.

From the next menu, select 1 for Edit Zone.

4.

Enter the zone number you wish to edit.

5.

From the next menu, select 3 for Zone Outputs.

6.

A screen similar to the one shown in Figure 7-4 will display. Select the event type you want to program
using the UP or DOWN key and press ENTER.

7.

Press the

or

key to toggle the group letter to either G = Group or T = output group template depend-

ing on want you need for this zone. Press

ENTER

.