Before You Begin Installing

151295

3-6

3.6.2

Current Draw Worksheet for SK SLC Devices

Use Table 3-2 to determine current requirements during alarm/battery standby operation when SK SLC devices
are installed. (Copy the page if additional space is required.) You can install up to 50 SK detectors and 50 SK
modules.

Table 3-2: Current Calculation Worksheet for SK Devices

Device

# of

Devices

Current per Device

Standby

Current

Alarm

Current

For each device use this formula: This column X This column = Current per number of devices.

Fire Panel (Current draw from
battery)

1

Standby: 200 mA

200 mA

Alarm: 365 mA

365 mA

Addressable SLC Detectors

SK-Photo

(50 max.)

1

Standby/Alarm: .30 mA

6

mA

mA

SK-Photo-T

mA

mA

SK-Ion

mA

mA

SK-Heat

mA

mA

SK-Heat-HT

mA

mA

SK-Acclimate

mA

mA

SK-Heat-ROR

mA

mA

SK-DUCT

5

mA

mA

SK-Beam (without integral test)

SLC

Standby/Alarm: 2 mA

mA

mA

Aux. Pwr

Standby: 2 mA

mA

Alarm: 8.5 mA

mA

SK-Beam-T

4

(with integral test)

(50 max.)

1

SLC

Standby/Alarm: 2 mA

Aux. Pwr

Standby: 2 mA

mA

Alarm: 8.5 mA

mA

SK-FIRE-CO

SLC

Standby: .30 mA

mA

Alarm: 7.2 mA

mA

Addressable SLC Modules

SK-Monitor

(50 max.)

1

Standby/Alarm .375 mA

mA

mA

SK-Minimon

mA

mA

SK-Pull-SA/SK-Pull-DA

SK-Monitor-2

Standby/Alarm: .75 mA

mA

mA

SK-Mon-10

Standby/Alarm: 3.5 mA

mA

mA

SK-Control

SLC

Standby: .375 mA

Alarm: .375 mA

mA

mA

Aux Pwr

Standby: 1.7 mA

mA

Alarm: 7 mA

mA

SK-Control-6

SLC

Standby: 2.25 mA

Alarm: 2.25 mA

mA

mA

Aux Pwr

Standby: 8 mA

mA

Alarm: 20 mA

mA

SK-Relay

Standby/Alarm: .255 mA

mA

mA

SK-Relay-6

Standby/Alarm: 1.45 mA

mA

mA

SK-RelayMon-2

Standby: 1.3 mA

mA

Alarm: 24 mA

mA