To table 7-6 for – SilentKnight 5700 User Manual

Page 117

Advertising
background image

Model 5700 Installation and Operation Manual

151295

7-19

11. Repeat Steps 1 through 15 for all circuits.

Table 7-5 Menu choices for Internal/External Power Modules

Choices

Type Selections

Function

Selections for

each Type

Comments

Enter Point or
Circuit

Select Type

UNUSED

NOTIF OUT

CTRL CKT

AUX PWR

CONSTANT

Constant auxiliary power.

RESETTABLE

Resettable auxiliary power.

DOOR

Door holder auxiliary power.

SOUNDER SYNC

Sounder Sync auxiliary power.

B SWITCH

MAN PULL

Refer to comments column of
Table 7-5 for description of these
options

Latch or Non-latching feature only
appears for waterflow, supervisory,
tamper, zone aux1, zone aux2, system
aux1, and system aux2

WATERFLOW

SUPERVSY

TAMPER

FIREDRILL

SILENCE

RESET

PAS_ACK

ZN_AUX1

ZN_AUX2

SYS_AUX1

SYS_AUX2

MAN REL

ILOCK

STATUS POINT

Non-latching - Used to activate an
ancillary Output Group that does not
active alarm, sound PZT, display status
or report events. Reset has no affect on
this point

A SWITCH

Same as B SWITCH

B DETECTOR

2-WIRE SMK

Used for Class B, 2-wire detectors

4-WIRE SMK

Used for Class B, 4-wire detectors

4-WIRE CO SMK

Used for Class B, 4-wire CO detectors

A DETECTOR

2-WIRE SMK

Used for Class A, 2-wire detectors

4-WIRE SMK

Used for Class A, 4-wire detectors

4-WIRE CO SMK

Used for Class A, 4-wire CO detectors

Select Group

Group or Zone selection will appear
depending on the type selected

Edit Name

See Section 7.5.4.