SilentKnight 5700 User Manual

Page 116

Advertising
background image

Programming

151295

7-18

7.5.2

Point Programming For Internal or External Power Module

To program for an internal or external power module points, follow these steps:

1.

Enter the installer code.

2.

Select 7 for Program Menu.

3.

Press 4 to enter point menu.

4.

Press the

or

arrows to select the desired module. Press

ENTER

. Refer to Section 6.5 for available

choices.

5.

Enter the number of the circuit or point you wish to edit. Refer to Table 7-6 for available selections.

6.

Press

ENTER

.

7.

Select the type by pressing the

or

arrows, then press

ENTER

.

8.

Select the function by pressing the

or

arrows, then press

ENTER

.

9.

Select the group by pressing the

or

arrows, then press

ENTER

.

10. Edit point name. Press

to skip point name edit. See Section 7.5.4.

SLC Loop

(cont.)

RELAY

OUTPUT PT

Select Group

Output Point, a general use relay type. Use for
applications requiring a relay, such as elevator
recall.

AUX RESET

Use for auxiliary power, resettable applications.
See Section 4.11.2.3 to learn how this option
operates.

AUX DOOR

Use for auxiliary power, door holder applications.
For example, if you were using an auxiliary power
supply for door holders, you would use this option.
See Section 4.11.2.1 for a description of how this
option operates.

Table 7-4: Point Programming

Module Type

Type

Selection

Function

Latching

Option

Comments