Compaq 2000 User Manual

Page 47

Advertising
background image

4-4 Compaq 2000 Series UPS Operation and Reference Guide

Table 4-1

Configuration Parameters/LED Indicators

Parameter

(LED)

Parameter

Name

LED 16

Status

Explanation

1

120/230 Nom

On

1

Nominal utility voltage level is
120/230 VAC.

2

110/220 Nom

On

1

Nominal utility voltage level is
110/220 VAC.

3

127/240 Nom

On

1

Nominal utility voltage level is
127/240 VAC.

10

100/208 Nom

On

1

Nominal utility voltage level is
100/208 VAC.

4

Extended

Voltage

On

UPS will supply utility power if the utility
voltage is within +20% to –35% of the
nominal voltage. If the utility voltage is
outside this range, the UPS will supply
battery power.

Off

(default)

UPS will supply utility power if the utility
voltage is within

±

20% of the nominal

voltage. If the utility voltage is outside this
range, the UPS will supply battery power.

5

Wiring

Fault

On

(default)

Enables an audio alarm if ground is
missing, or if line and neutral connections
have been reversed.

Off

Disables the audio alarm for this event.

6

Low

Battery

On

(default)

Enables an audio alarm 3 minutes before
battery shutdown.

Off

Enables an audio alarm 5 minutes before
battery shutdown.

7

Shutdown

Delay

On

(default)

Enables a 5-second delay before turning
off power to the output receptacles after
receiving a shutdown command from the
host.

Off

Enables a 3-minute delay.

continued