Changing configuration parameters – Compaq 2000 User Manual

Page 49

Advertising
background image

4-6 Compaq 2000 Series UPS Operation and Reference Guide

Changing Configuration Parameters

The Configure mode can be entered from the Operate or Standby mode.

IMPORTANT: If the STANDBY button is pressed while in the Configure mode, the UPS will
enter Standby mode, and power to the load segments will cease.

2

3

4

1

Figure 4-3. Configure mode controls

1 ON LED (LED 16)
2 ON button
3 STANDBY button
4 TEST/ALARM RESET button

To change configuration parameters:

1.

Place the UPS in Configure mode by pressing the ON (

2) and

TEST/ALARM RESET (

4) buttons simultaneously. Release the buttons

when the acknowledgement beep sounds.

2.

The top left LED on the front panel LED display should begin to blink,
indicating that configuration parameter 1 is selected.

3.

To determine if the selected configuration parameter value is ON or

OFF, check LED 16 (

1)—if LED 16 is ON, the selected parameter is

also ON.

4.

To toggle the selected configuration parameter value, press the

TEST/ALARM RESET button (

4). The UPS will acknowledge

compliance with a short beep.

Advertising