Configuration 4-9

If the utility voltage frequently varies outside the UPS operating range
(see Fig 4-6), consider changing from normal to extended range
(+20% to –35%). This provides more tolerance to brief utility voltage
fluctuations.

To update the nominal voltage and operating range parameters:

1.

Have a qualified electrician monitor utility voltage.

2.

Use the following tables to identify the operating range that most closely
matches requirements:

Table 4-2

Operating Ranges (VAC) - T2000 and T2000j Models

Nominal Level

Normal Range

Extended Range

100

80 to 120

Not applicable

110

88 to 132

72 to 132

120

96 to 144

78 to 144

127

102 to 152

83 to 155

Table 4-3

Operating Ranges (VAC) - T2000h and T2000h-NA Models

Nominal Level

Normal Range

Extended Range

208

166 to 250

Not applicable

220

176 to 264

143 to 264

230

184 to 276

150 to 276

240

192 to 288

156 to 288

3.

For nominal voltage level setting, select configuration parameters
1, 2, 3, or 10 (see Table 4-1).

4.

Access parameter 4 to switch from normal to extended range (see
Table 4-1).