3 sdm-sio4 configuration examples, Example cr10x program – Campbell Hausfeld Serial I/O Interface SDM-SIO4 User Manual

Page 44

Advertising
background image

SDM-SIO4 User Guide

5-14

5.2.22 Command 2305: Transmit Byte(s)

By using P113 command 2305 it is possible to transmit either one or two bytes
from the command options. If any command option is set to 999 then the byte will
not be sent. The number range for each command option is 0-255 and 999. An
example of its use is below:

1:SDM-SIO4 (P113)

1:1

Reps.

2:0

SDM address.

3:1

Mode, send bytes to port 1.

4:2305

Command.

5:13

Decimal number that represents Carriage Ret.

6:10

Decimal number that represents Line Feed

7:0000

Values/Rep.

8:0000

Start location.

9:1

Mult.

10:0.0 Offset.

The example will transmit the bytes ‘carriage return line feed’ (CrLf) to port one.

Values per repetition = 0

5.3 SDM-SIO4 Configuration Examples

Although the serial port configurations can be set up using the ‘command line’,
many users may prefer to set up the ports from their program. This would
normally be done once when the program is first compiled. The instruction can be
placed within a logical block which only runs when a specified datalogger flag is
reset. The program should be written so that the flag can then be set to prevent the
instruction running after the first execution; this also enables you to force
reconfiguration by toggling the flag low.

Example CR10X Program

This program is an example of how you could set up the SDM-SIO4 serial mode
and filter type once on program compilation or if flag 1 was reset. This
works on port 1 of the SDM-SIO4.

The program will convert ASCII floating point input values into Campbell
Scientific floating point format. The datalogger will store two values in locations
1 and 2.

*Table 1 Program

01: 2 Execution Interval (seconds)

;if flag one is not set then set up the serial mode and filter.

1: If Flag/Port (P91)

1: 21 Do if Flag 1 is Low

2: 30 Then Do

Advertising