Section 5. Programming the Datalogger

5-23

– see ‘SDM Port’ in Section 1 for details. This should be connected to control port
8 for this example.

A typical filter that could be used is as follows:

fltst 200 "t[data]A5xff"

This filter works as follows:

t[data] – this filter waits for an exact string match before it starts the next filter. In
this case it is waiting for the sensor to send the string ‘data’.

A5 – this filter sets up a 250ms filter time out. This time out should be long
enough for the sensor to transmit all of its data.

x – this filter marks the start of the data set. In this case the data set is two floating
point numbers.

f – this filter searches for the first ASCII floating point number to convert.

f – this filter searches for the second ASCII floating point number to convert.

*Table 1 Program

01: 2 Execution Interval (seconds)

;set control port 8 to i/p so it can be used as an interrupt

1: Set Port(s) (P20)

1: 8999 C8..C5 = input/nc/nc/nc

2: 9999 C4..C1 = nc/nc/nc/nc

;do filter setup only if flag one is clear

2: If Flag/Port (P91)

1: 21 Do if Flag 1 is Low

2: 30 Then Do

;set up string filter

3: SDM-SIO4 (P113)

1: 1 Reps

2: 0 Address

3: 1 Send/Receive Port 1

4: 2054 Command

5: 9200 1st Parameters

6: 0 2nd Parameters

7: 0 Values per Rep

8: 0 Loc [ _________ ]

9: 1.0 Mult

10: 0.0 Offset

;delay required by filter setup command

4: Excitation with Delay (P22)

1: 1 Ex Channel

2: 0 Delay W/Ex (units = 0.01 sec)

3: 1 Delay After Ex (units = 0.01 sec)

4: 0 mV Excitation

;set flag one high so the filter set-up is only done once

5: Do (P86)

1: 11 Set Flag 1 High