I /in, 1r] is/in – Cooper Lighting Low Impedance Bus Differential Relay M-LIB3 User Manual

Page 24

Advertising
background image

M-LIB3 Low Impedance Bus Differential Relay

24

To compensate the differential current produced by CT’s error or saturation, the actual minimum operation
level I

S

is dynamically adjusted in function of the actual through current I

R

according to the set coefficient [1R],

[2R]

I

R

< [1I

R

]

: I

S

= I

dS

[1I

R

] < I

R

< [2I

R

]

: I

S

= I

dS

+ 1R(I

R

-[1I

R

])

ƒ

I

R

> [2I

R

]

: I

S

= I

dS

+ 1R([2I

R

]-[1I

R

]) + 2R(I

R

-[2I

R

])

BIAS SATURATION : I

S

= 10 In for any I

R

[2I ]

R

I

R

[I /In]

ds

I

R

I

ds

R=

[2R]

I

ds

I /In

R

[1I ]

R

ƒ

[1R]

Is/In

I

ds