2.4 F/C Rack Panel

19” 3U rack panel suitable to house up to seven plug-in modules type M-BF3 or M-BC3 including

back printed circuit board with :

q

Diodes for supply of the measurement bus of two Main Zones and one Check Zone

q

7 Female sockets for plug-in connection of the M-BF3 or M-BC3 modules.

q

7 Terminal boards with screw terminals for connection to the system.

q

1 Male connector socket for interfacing with the differential protection relays.

q

1 Female connector socket for interconnection with other F/C Rack Panels.

q

1 Power supply module:

The auxiliary power is supplied by a built-in interchangeable module fully isolated and self
protected. Two options are available

:

24V(-20%) / 110V(+15%) a.c.

80V(-20%) / 220V(+15%) a.c.

a) -

b) -

24V(-20%) / 125V(+20%) d.c.

90V(-20%) / 250V(+20%) d.c.

Before energizing the unit check that supply voltage is within the allowed limits.

Power consumption : nx 4W (n = number of modules M-BF3)
The unit can supply up to 12 modules M-BF3 plus two modules M-BC3 (one unit can supply two F/C Rack
Panels).