M-lib3 low impedance bus differential relay – Cooper Lighting Low Impedance Bus Differential Relay M-LIB3 User Manual

Page 26

Advertising
background image

M-LIB3 Low Impedance Bus Differential Relay

26

6.6

SIGNALIZATIONS

Eight signal LEDs (normally off) are provided:

a) Red LED

dA>

q

Flashing when I

d

A > [I

ds

].

q

Illuminated on tripping of the biased differential element : I

d

A > I

S

b) Red LED

dB>

q

Flashing when I

d

B > [I

ds

].

q

Illuminated on tripping of the biased differential element : I

d

B > I

S

c) Red LED

dC

>

q

Flashing when I

d

C > [I

ds

].

q

Illuminated on tripping of the biased differential element : I

d

C > I

S

d) Red LED

dvs

q

Flashing during supervision time delay

q

Illuminated on tripping of the CT’s Supervision element.

e) Yellow LED

PROG/

I.R.F.

q

Flashing during the programming of the parameters or in case of
Internal Relay Fault.

f)

Red LED

Remote

Trigger

q

Illuminated when the oscillography trigger input is activated

g) Red LED

Time

Sync.

q

Illuminated when synchronization input is active

h) Yellow LED

BLOCK

INPUT

q

Flashing when digital input B1 is activated

The reset of the LEDs takes place as follows

q

From flashing to off, automatically when the lit-on cause disappears.

q

From ON to OFF, by "ENTER/RESET" push button only if the tripping cause has disappeared.

In case of auxiliary power supply failure the status of the LEDs is recorded and reproduced when power supply
is restored.

dB>

PROG/

I.R.F.

BLOCK

INPUT

a

b

c

d

e

f

g

h

REMOTE

TRIGGER

TIME

SYNC.

dvs

dC>

dA>

Advertising