6.15.2 PROGRAMMING THE CONFIGURATION OF OUTPUT RELAYS

Mode PROG menu F

RELAY (Production standard settings here under shown).

The key "+" operates as cursor; it moves through the numbers corresponding to the four programmable relays
in the sequence 1,2,3,4,(1= relay R1, etc.) and makes start flashing the information actually present in the
digit. The information present in the digit can be either the number of the relay (if this was already associated
to the function actually on programming) or a dot (-) if the relay was not yet addressed.
The key "-" changes the existing status from the dot to the relay number or vice versa.
After having programmed all four relays, press “ ENTER “ to validate the programmed
configuration.

Display

Description

Is

1---

Bias Differential element operates relay R1 eventually plus R2, R3, R4 as programmed
(one or more)

Ids

-2--

Un-biased differential element operates relay R2, R3, R4 as programmed

Isv

--3-

Time delayed CT supervision element operates relay R2, R3, R4 as programmed

FRes: Aut.

Reset of output relays after tripping is:
Aut. = Automatic Man. = Manually key Enter /Reset or via serial bus

d> - 2 - 4

This dash means

that output relay

number 1 is not
assigned to this

element

This is the name

of protective

element

The number 2

means that

output relay 2

will operate

when this

This dash

means that

output relay

number 3 is not
assigned to this

element

The number 4

means that output

relay 4 will operate

when this element

trips