M-LIB3 Low Impedance Bus Differential Relay

30

6.14 READING OF PROGRAMMED SETTINGS AND RELAY'S CONFIGURATION

Enter the mode "SET DISP", select the menu "SETTINGS" or "F

RELAY", scroll information available in the

menu by keys "+" or "-".
SETTINGS= values of relay's operation parameters as programmed
F

RELAY= output relays associated to the different functions as programmed.

6.15 PROGRAMMING

The relay is supplied with the standard default programming used for factory test. [ Values here below reported
( ----- ) ].
All parameters can be modified as needed in the mode PROG and displayed in the mode SET DISP
Programming is enabled only if no input current is detected (main circuit breakers open).
As soon as programming is enabled, the LED PRG/IRF flashes and the reclosing lockout relay R5 is de-
energized. Enter MODE "PROG" and SELECT either "SETTINGS" for programming of parameters or
"F

RELAY" for programming of output relays configuration; enable programming by the indirect operation key

PROG.
The key SELECT now scrolls the available parameters. By the key (+) , (-) the displayed values can be
modified; to speed up parameter's variation press the key SELECT while "+" or "-" are pressed.
Press key "ENTER/RESET" to validate the set values.

6.15.1 PROGRAMMING OF FUNCTIONS SETTINGS

Mode PROG menu SETTINGS. (Production standard settings here under shown).

Display

Description

Setting Range

Step

Units

xxxxxxx

Current date

DDMMMYY

-

-

xx:xx:xx

Current time

HH:MM:SS

-

-

Fn 50 Hz

System frequency

50 - 60

10

Hz

Ids 0.2 In

Basic minimum pick-up level of differential element

0.2 – 2 – Dis

0.01

In

trf 1 s

Trip time delay of the Relay’s Internal Fault Detector

0.1 – 9.9

0.1

s

BI OFF

Blocking Input enable

OFF – ON

-

-

1R 0.5 pu

Bias coefficient in the zone [1I

R

] <I

R

< [2I

R

]

0.4 – 1

0.01

pu

1IR 1 In

Action starting level for 1R

0.5 – 2.0

0.1

In

2R 1.0 pu

Bias coefficient in the zone I

R

> [2I

R

]

0.4 – 1.00

0.01

pu

2IR 6 In

Action starting level for 2R

3 – 8

0.1

In

Isv 0.2 In

Minimum pick-up level of CT supervision element

0.1 – 1 - Dis

0.01

In

tsv 1 s

Time delay of the C.T Supervision element

0.1 – 9.9

0.1

s

TRG: Ext

Trigger for oscillography records is Internal or External
(via digital input B3)

Ext - Ids

Is – Isv

-

-

Tsyn Dis m

Synchronization time internal

5-10-15

30-60-Dis

-

-

NodAd 1

Identification number for connection on serial
communication bus

1 - 250

1

-

The setting Dis indicates that the function is disabled.

In 500 Ap

In is the unit of

measure,

0.2 is the

setting
default

Ids is the

name

of the variable