COOLING AND VENTILATING AIR

It is absolutely essential that an adequate flow of air

for cooling, ventilating and engine combustion be sup­
plied to the generator set. Without sufficient air flow,
the engine-generator quickly overheats. Such over­

heating can cause serious operating difficulties and
may also cause fire and personal injury. The installer
must make sure that sufficient air is available to the
generator for cooling, ventilating and combustion. The
installer must also provide for a path for exhausting

the cooling air to the exterior of a compartment, if so

equipped.

DANGER; NEVER USE DISCHARGED COOLING

AIR FOR HEATING OR PERMIT SUCH AIR TO
ENTER THE VEHICLE INTERIOR. THIS AIR CON­

TAINS DEADLY CARBON MONOXIDE GAS AND
OTHER POISONOUS, FLAMMABLE OR EXPLO­

SIVE GASES.

GENERATOR AIR FLOW

Engine operation drives cooling fans for the 2-stage

cooling air system. A pressure fan draws cooling air
into the top of generator and into the side of the con­

trol panel (Figure 20). This air flow cools the engine-
generator and electronic components. The second

part of cooling system, a suction fan, draws air that is
heated from a hot engine into a collector pan at the
base of the unit. This heated air (although cooler than
exhaust muffler) is directed across the muffler to cool
it. The heated air flow is then deflected out the bottom

toward the ground.

Figure 20 — Air Flow Through Engine-Generato

COOLING AIR INLET OPENINGS

Ideally, you should provide three air inlet openings,

whether the generator is housed in a conventional

compartment or not. Two of the openings should be
10 square inches and located as shown in Figure 21.

The third opening should provide for a minimum of 40
square inches unrestricted and be located lower on
the compartment door.

NOTE: Screening, louvers, or expanded metal that
cover air openings restrict air flow that you must com­
pensate for by making the actual air opening propor­

tionately larger. See “Compensating for Restrictions.”

Figure 21 — Air Inlet in Compartment Door

10 SQUIRE INCHES

(OPTIONAL OPENINGS)
40 SQUIRE INCHES UNRESTRICTED

(MINIMUM OPENING)

For conventional compartment mounted units, the air
inlet is generally provided in the compartment door.

IMPORTANT: IF YOU PLAN TO INSTALL THE GEN­
ERATOR

IN A COMPARTMENT, BE SURE TO

LEAVE AT LEAST ONE (1") INCH OF CLEARANCE
BETWEEN

THE

GENERATOR

AND

COMPART­

MENT WALLS AND CEILING. INCLUDE 26 GAUGE
GALVANIZED STEEL LINING AND SOUND INSULA­

TION WHEN YOU MEASURE FOR THIS 1 INCH

CLEARANCE.

When the unit is installed on a suspended mounting
system, one of several different methods of supplying
air flow may be used as follows:

• Provide a door in the vehicle skirt having an air inlet

opening (Figure 22).

Figure 22 — Suspended Mount: Inlet Door

19