BATTERY INSTALLATION

RECOMMENDED BATTERY

Install a battery that

meets the

following require­

ments:

• Battery must be a 12 volt, automotive type storage bat­

tery.

• For prevailing ambient temperatures above 32°F (0“C),

use a battery rated 70 amp-hours and capable of deliver­

ing 360 cold cranking amperes.

• For prevailing ambient temperatures below

32°F

(0°C),

use a battery rated 95 amp-hours and capable of deliver­

ing 450 cold cranking amperes.

IMPORTANT: IF THE BATTERY IS TO BE USED TO
POWER

OTHER

VEHICLE

ACCESSORIES,

AS

WELL

AS

START

THE

GENERATOR,

YOU

MAY

NEED A BATTERY WITH A LARGER CAPACITY.

BATTERY CABLES

Using battery cables that are too long or too small in

diameter may cause a drop in voltage which causes
starting problems. For best cold weather starting, the
voltage drop between battery terminals and the gen­
erator connection point should not exceed 0.12 volts
per 100 amperes of cranking current.

Select battery cables based on (a) cable length, and
(b)

prevailing

ambient

temperatures.

Generally,

the

longer the cable and the colder the weather, the larg­
er the cable size must be as shown in the chart
below.

CABLELENGTH

in Feet (meters)

CABLE SIZE

Oto 10 (Oto 3)

2*

11 to 15 (3.4 to 4.5)

0

16 to 20 (4.5 to 6)

000

‘For warm weather, use No. 2 cable up to 20 feet.

_

25

~