Direct vent fpual, Roof vent system – Adams Condensing Oil-Fired Furnace User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Installations require both a vent/flue pipe and a

combustion air intake pipe. Refer to the

appropriate section for details concerning piping

size, length, number of elbows, furnace

connections, and terminations.

DIRECT VENT fPUAL

P\PE\

PIPING -

BECKETT NX
NON-DIRECT VENT fPUAL PIPE^

INTERburner

Installations require both a combustion air intake

and a ventrue pipe. The pipes may be run

horizontally and exit through the ^de of the

building or run vertically and exit through the

roof of the building.

The pipes may be run through an existing

unused chimney; however, they must extend a

minimum of 12 inches above the top of the

chimney.

The space between the pipes and the chimney

must be closed with a weather tight, corrosion

resistant flashing. Both the combustion air

intake and vent/flue pipe terminations must be in

the same atmospheric pressure zone.

Refer to Section VI, Vent/flue and Combustion

air Pipe - Termination Locations or Concentric

Vent Termination for specific details on

termination construction.

For details concerning connection of pipes to the

furnace, refer to the Section VI, Vent/Flue Pipe

and Combustion Pipe - Standard Furnace

connections or alternate furnace connections.

Horizontal terminations should be as shown in

the following figure. Refer to Section Vi,

Vent/Flue Pipe and Combustion Pipe -

Termination Location for location restrictions,

A 3 Î4 inch diameter hole is required for 3”

diameter pipe. To secure the pipe passing

through the wall and prohibit damage to piping
connections, a coupling should be installed on

either side of the wall and solvent cemented to a

pipe connecting the two couplings.

The pipe length should be the wall thickness

plus the depth of the socket fittings to be

installed on the inside and outside of the wall.

The wall penetration should be sealed with

silicone caulking material.

ROOF VENT SYSTEM

The vent termination of vent pipe run vertically

through a roof must terminate at least 12 inches

above the roof line (or the anticipated snow

level) and be at least 12 inches from any vertical

wall (including any anticipated snow build up).

Standard horizontal Terminations (Dual Pipe)

Vertical Terminations (Dual Pipe)

Alternate

Horizontal

Vent

Termination

(Dual

Pipe)

11

Advertising