Inspect fitter frequently, Xi. start-up procedure & adjustment – Adams Condensing Oil-Fired Furnace User Manual

Page 18

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

When the furnace is used in connection with

a cooling unit, the furnace should be

installed in parallel with or on the upstream

side of the cooling unit to avoid

condensation in the heating element. With

a parallel flow arrangement, the dampers or

other means used to control the flow of air

must be adequate to prevent chilled air from

entering the furnace and, if manually

operated, must be equipped with means to

prevent operation of either unit unless the

damper is in the full heat or coot position.

FILTERS - READ THIS SECTION BEFORE

INSTALLING THE RETURN AIR

DUCTWORK

A FILTER MUST BE USED WITH THIS

FURNACE. Discuss filter maintenance with

the building owner. Filters are shipped with

this furnace. Filters must comply with UL900

or CAN/ULCS111 standards.

If the furnace is installed without filters, the

warranty will be voided.

Inspect Fitter Frequently!

Replace 3 times each heating season.

XI. START-UP PROCEDURE &

ADJUSTMENT

Please read the procedures outlined below

and familiarize yourself with the appliance

sequence of operation before conducting

any tests or starting the appliance.

Note;

A separate start-up form is attached

to the instailation instructions and must be

completed and returned to the

manufacturer for warranty registration

within 30 days of installation.

Check that furnace is instaiied level. This is

important since the secondary heat

exchanger is pitched at 3 degrees for proper

condensate drainage. Check with a

carpenters ievel and shim accordingly.

Verify that the fuel supply lines are leak-

free. Inspect ait connections for air leaks.

Fuel system integrity is often assumed, but

cannot be overlooked. Test the fuel system

for integrity. Even a small leak can cause a

multitude of burner issues. Never use

compression fittings.

Verify pump pressure with appropriate test

instrument. (140 PSI) for Adams

INTERburner Mark 10 or Beckett NX.

Check pump seal by shutting off pump and

noting the pressure drop. The pump

pressure should drop approximately 20%

and hold indefinitely.

Prime

oil filter supplied with the appliance

before bleeding air from system. Purge the

oil pump of air in the system as soon as the

burner motor starts rotating by or>ening

bleeder valve on pump and catch oil in

suitable container.

Check post-purge timing on primary safety

controi by examining dip-switch

configuration on the primary control. This

controi is factory set at 8 minutes post purge

time.

Locate

fan control in blower compartment.

Check

blower-on

time delay. Set delay for

30 seconds.

Verify blower-off

delay setting at 390-600

seconds. This is required for proper heat

removal from the heat exchanger once the

thermostat is satisfied.

Do not

remove blower deck support bracket

located in the blower compartment. This

bracket may be confused for a shipping

bracket and must

not

be removed. This

bracket is installed in up-flow and counter­

flow models only. !t is a sheet metal

support bracket in the blower compartment.

Prime condensate drain trap with water.

Operate

the burner for (3) minutes on, (3)

minutes off twice. Operate the burner for

approximately 30-40 minutes to

cure the

internal ceramic fiber combustion

chamber.

Be aware of moderate

odor/smoke upon initial firing and gradually
diminishing to nomnal over the break-in

period. Note the air handler should be

operating at all times

during the break-in

period and final tuning.

You are now ready for the final fine-tuning.

The

burner air settings are approximate

and needs to be adjusted to the vent system

in the fteld for most efficient operation.

17

Advertising