Table 1 System and General Troubleshooting

PROBLEM

POSSIBLE CAUSE

REMEDY

Homs does not
heat evenly.

Improper distribution of heat.

This is unlikety to be a furnace i^'drlem. Balarx» duct system with dampers.

Supply air
temperature too
hot.

Airflow Uocked or dirty air filter.

Clean or replace air fitter.

Insufficient airflow.

Check all dampers. Open closed dampers including registers in unused rooms. Check

system temoereture rise. Iftemperature rise is too high, spaed uo blower fen.

Supply air
temperature too
cool.

Excess airflow.

Check system temperature rise. Slow down blower fen is necessary.

Excessive duct losses.

Check supply air ductwork. Sealleaky Joints and seams. Insulate ductwork if

necessarv-

Supply air
tempwature too
cool during first
moments of
furnace cyde.

Fan control "fiin on' setting too k3W,

incrrase fan on’fime. Register air deflectors may help.

Excessive duct losses.

Check supply air ductwork. Seal leaky joints and seams, (nsulata ductwork Ef
r>eces8ary.

XIV.

Maintenance

& Annual Inspection

1) Replace Delevan nozzle with exact capacity, angle and pattern as supplied.

2) Replace vestibule mounted oil filter with AF-1 filter.

3) Replace condensate neutralizer with part number CCR-1.

4) Remove air handler assembly (slide out) and inspect the bottom (upflow configuration) of the

secondary heat exchanger. Loosen accumulated foreign matter with soft brush and vacuum
clean.

5) Perform all routine safety switch function checks.

6) Perform combustion analysis as described on page 18 Burner Adjustment.

7) Do not remove rear access panel of heat exchanger. Internal cleaning of the primary or

secondary heat exchangers are not required (unless satisfactory combustion analysis

cannot be achieved).

! CAUTION

The ceramic combustion chamber located in the primary heat exchanger

should not

be handled

once it is cured at startup. Structural damage will occur, if handled and if broken the furnace will be
rendered inoperative.

NOTE:

If the secondary heat exchanger turbulators have a light coating of soot, this is normal and will not

affect the efficiency of the furnace.

22