Burner, Temperature rise, Temperature rise measurement – Adams Condensing Oil-Fired Furnace User Manual

Page 19: Circulator blower speeds

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Drill a 3/8” hole in the PVC exhaust vent piping

approximately 18" above where the PVC exits

the side of the furnace for your combustion

analysis equipment. (Seal with RTV silicone

when finished conducting combustion analysis).

BURNER

1) Operate burner for 15 minutes before

conducting test wortc.

2) Adjust burner settings until a trace (0-1 on

a smoke scale of 10) is obtained with smoke

test pump.

3) Read C02%. This should be

approximately 13.0%.

4) Increase air to burner to reduce C02% 1.0

to 1.5% less than where you were able to

obtain a trace of smoke.

77

j

/

s

procedure allows a margin of reserve for

variable conditions.

5) Re-check smoke to insure it is 0.

Your final C02% should be

approximately 11.5%

Check vent stack temperatures as beiow:

и

0

D
E
L

APPROX.

AMBIEtrr

PLUS

STACK

TEMP F.

INPUT

RATE

THERMAL

EFFICIENCY

50

20-24

56,000

97-99%

75

27-31

82,000

95-97%

100

29-33

100,000

94-96%

125

38-42

115,000

92-94%

Temperature Rise

Temperature rise must be within the range
below. An incorrect temperature rise may

result in condensing in or overheating of the

heat exchanger.

Detennine and adjust temperature rise as

follows:

Model

Temp. F.

Degree Rise

50-2.6

50-60

75-2.5

55-65

100-2.5

60-70

50-5

30-40

75-5

35-45

100-5

45-55

125-5

50-60

1

.

2

.

Operate furnace with burner firing for

approximately ten minutes. Ensure all

registers are open and all duct dampers are

in their final (fully or partially open) position.

Place thermometers in the return and supply

ducts as close to the furnace as possible.

Thermometers must not be influenced by

radiant heat by being able to "see" the heat

exchanger

HEAT EXCHANGER

RADIATION TJ NE OF SIGHT-

3.

4.

Temperature Rise Measurement

Subtract the return air temperature from

the supply air temperature to determine the

air temperature rise. Allow adequate time

for thermometer readings to stabilize.

Adjust temperature rise by adjusting the

circulator blower speed. Increase blower

speed to reduce temperature rise.

Decrease blower sp^ to increase

temperature rise.

Set thermostat heat anticipator setting at 0.2 A

as a base point. Operate furnace and measure

anticipation amperage and adjust thermostat to

manufacturer's instructions.

CIRCULATOR BLOWER SPEEDS

This furnace is equipped with a multi-speed

circulator blower. This blower provides ease in

adjusting blower speeds These blower speeds

should be adjusted by the installer to match the

installation requirements so as to provide the

correct heating temperature rise and correct
cooling CFM.

To adjust the circulator blower speed, proceed
as follows;

1. Turn OFF power to the furnace.

Relocate desired motor leads to the

circulator blower terminals on the terminal

block as required.

Turn ON power to furnace.

Verify proper temperature rise as outlined in

Section XIV, Startup Procedure and

Adjustment - Temperature Rise.

2

.

3.

4.

18

Advertising