1.4.6 I/O refreshing rate of an HSL system

The scan time unit for one slave index is set in 3/6/12 Mbps trans-
mission rate. Once the maximum slave address is set, the polling
cycle time of the HSL system is using the following formula:

Polling cycle time = maximum-address-of-slave * scan time unit

Table 1-5: Polling cycle time of HSL (Full Duplex Mode)

Note:

Regardless of the transmission rate you select, the minimum

polling cycle time is 3×scan time unit, even when the maxi-

mum address is less than 3. Refer to Appendix A.

Maximum

address

Cycle Time

under 3 Mbps

Cycle Time

under 6 Mbps

Cycle Time

under 12 Mbps

5

303.33 µs

151.67 µs

75.83 µs

10

606.67µs

303.33 µs

151.67 µs

20

1.213 ms

606.67 µs

303.33 µs

30

1.820 ms

910.00 µs

455.00 µs

40

2.427 ms

1.213 ms

606.67 µs

50

3.033 ms

1.516 ms

758.33 µs

60

3.640 ms

1.820 ms

910.00 µs

63

3.822 ms

1.911 ms

955.50 µs