P.41

Replacement, Removal or addition for PDU & IP dongle

1. How to replace the failed IP dongle ?

Step 1

- Prepare a new IP dongle.

Step 2

- Disable alarm email in <Alarm> page.

Step 3

- Replace the failed IP dongle with the new one on 1st level PDU.

Step 4

- Confi gure the setting of the new IP dongle same as the old one.

(Please refer to user manual < 2.2 > for details)

Step 5

- Click Start Connection in <Status> page for the relevant IP dongle.

Step 6

- Enable alarm email in <Alarm> page again.

2. How to replace the failed 1st level PDU with a new one ?

Step 1

- Prepare a new PDU and set the PDU to 1st level.

(Please refer to user manual < 1.2 > display 9.1 for details)

Step 2

- Disable alarm email in <Alarm> page.

Step 3

- Power off & unplug the device(s) which connected to the PDU.

Step 4

- Power off & remove the failed 1st level PDU from connection.

Step 5

- Install the IP dongle on the new 1st level PDU.

Step 6

- Install and connect the new PDU.

Step 7

- Power on the new PDU and connect to the device(s).

Step 8

- Click Start Connection in <Status> page for the relevant IP dongle.

Step 9

- Confi gure the new PDU in <Details> and <TH Sensor> page such as Alarm Amp , Name,

Location

Step 10

- Enable alarm email in <Alarm> page.

3. How to replace a failed certain level PDU with a new one ?

Step 1

- Prepare a new PDU and set the PDU level accordingly.

(Please refer to user manual < 1.2 > display 9.1 for details)

Step 2

- Prepare an appropriate length Cat. 5/6 cable.

Step 3

- Click Set maintenance in <Details> page for the failed PDU.

Step 4

- Use the Cat. 5/6 cable to bridge over the failed PDU which will be replaced to minimize log/

data loss.

Step 5

- Power off & unplug the device(s) which connected to the failed PDU.

Step 6

- Power off & remove the failed PDU from connection.

Step 7

- Install the new PDU, cancel the cable-bridging and reconnect the

PDU to the last and next one.

Step 8

- Power on the new PDU and connect to the device(s).

Step 9

- Click Remove maintenance in <Details> page for the new PDU.

Step 10

- Confi gure the new PDU in <Details> and <TH Sensor> page such as Alarm Amp, Name,

Location

Ignore step 2 & 4 if the failed PDU is in the last level.