< 1.3 > Temp. & Humidity Sensor Connection & Specifi cation

Temp. & Humid. Sensor

Part no.

IG - TH01

Temperature
Sensitivity

Range

0 to 80°C ( 32 to 176°F )

Accuracy

±1.0°C typical ( ±2°F )

Resolution

0.1°C ( 0.2°F )

Response Time

5 to 30 sec

Relative
Humidity
Sensitivity

Range

0 to 100% R.H

Accuracy

0 to 100, ±8.0% R.H

20 to 80, ±4.5% R.H.

Resolution

1% R.H.

Response Time

8 sec

Power
Requirement

Voltage

12VDC, powered by sensor port

Current Consumption

20mA

Power consumption

0.24 Watt

Power on indicator

Red LED

Housing

Chassis & Cover

plastic

Color

Dark gray

Installation

Magnetic base for unrestricted installation

Cable

Cable Length

TH sensor w/ 2m cable ( standard )

TH sensor w/ 4m cable ( option )

Cable Specifi cation

4-wired 3.5mm to RJ11

Cable Color

Black

Environmental

Operating

0 to 80°C Degree

Storage

-5 to 80°C Degree

Humidity

0~100%, non-condensing

Dimensions

Product

30L x 25Wx 18H mm

Weight

Net

10g

Compatibility

InfraPower

W / WS / Wi / WSi series PDU

InfraSolution

X-2000 series

InfraGuard

Cabinet sensor system