< 5.2 > Replacement, Removal or addition for PDU & IP dongle

4. How to move out a PDU (without a replacement) ?

Step

1. Prepare an appropriate length Cat. 5/6 cable.

Step

2. Disable alarm email in <Alarm> page.

Step

3. Use the Cat. 5/6 cable to bridge over the removed PDU to minimize log/data loss.

Step

4. Power off & unplug the device(s) which connected to the PDU.

Step

5. Power off & remove the PDU from connection.

Step

6. Click Disable Monitoring in <Details> page to stop monitoring the removed PDU.

Step

7. Enable alarm email in <Alarm> page.

If the removed PDU NOT in the last level, you MUST reconfi gure and reset the level for the

affected PDU(s) which next to the removed PDU.

Ignore step 1 & 3 if the removed PDU is in the last level.

5. How to add an extra PDU to an existing PDU group ?

Step

1. Prepare a PDU and set the PDU level accordingly.

(Please refer to P.1 for the PDU level setting )

Step

2. Prepare an appropriate length Cat. 5/6 cable.

Step

3. Disable alarm email in <Alarm> page.

Step

4. Install and connect the new PDU.

Step

5. Power on the new PDU.

Step

6. Click Search in <Status> page to search the new installed PDU.

Step

7. Confi gure the new PDU in <Status> and <Details> page such as

Alarm Amp , Name, Location

Step

8. Enable alarm email in <Alarm> page.

If the added PDU NOT in the last level, you MUST reconfi gure and reset the level for the

affected PDU(s) which next to the added PDU.