Austin Hughes IPM-01 User Manual

Page 33

Advertising
background image

www.austin-hughes.com

UM-IPM-01-Q213V2

P.29

< 4.3 > Meter for MTS & MT PDU

1. What is feature of the MT PDU?
The MT PDU offers simple & highly reliable power distribution to multiple equipments, and built-in a
digital ampere meter indicates the total power consumption of equipment connected to the PDU. The
digital ampere meter has an interface which can connect to an IP dongle to the ethernet network, which
allows managers to real-time remote monitor the PDU load thru the InfraPower manager (IPM-01).

2. What is feature of the MTS PDU?
The MTS PDUs offers the same features as MT PDUs, with an addition remote control power capability
to individual PDU outlets. The remote outlet power control allows power on/off functionality for power
recycling to reboot locked-up equipment and to avoid unauthorized use of individual outlets.

3. Which types of outlet can MTS PDU support?
The MTS PDU supports IEC 60320/C13, IEC 60320/C19, NEMA 5-15/20R & BS1363 outlet type.

4. Can the MTS and MT PDUs cascade together?
Yes, the MTS & MT model PDUs can connect together as a cascade chain.

5. If one of the cascaded MTS / MT PDU loses power, will it affect other PDUs in the same
chain?
No, the other cascaded MTS / MT PDUs in upper & lower level will not be affected.

6. What is the maximum cabling distance between two cascaded PDUs?
Up to 20 meter (66 feet) of CAT. 5 / 6 cable.

7. What is the maximum cascade level of the MTS / MT PDU in a chain?
16 levels

< 4.4 > Others

1. Does the InfraPower PDU has the overpower protection?
Yes, the PDU provides the resettable fuse or optional circuit breaker for the overpower protection.

2. What is the standard inlet cable length of InfraPower?
3 meter ( 9.9 feet ).

3. Where can I fi nd the Catalogue / User manual /Model list / Wire diagram of InfraPower
PDUs?
Please visit the www.austin-hughes.com

4. How can we get a further support?
Please send the email to [email protected] or [email protected]