Setup parameters, Parameter tables, Etup – Bonaire Touchpad Control (LV) - Tekelek User Manual

Page 20: Arameters, Arameter, Ables, Setup & commissioning

Advertising
background image

Touch Pad Control

Setup & Commissioning

TEK600 Series Control

Page 20

Setup Parameters
There are a series of available parameters that can be modified to tailor the control to meet the customer’s requirements.

Carefully read these tables before entering the maintenance modes.

There are a number of potential product classes that the touch

pad control system will control. The class is the first

requirement for selection when entering the maintenance
mode.

Parameter Tables

Water Management

Installer Maintenance

Parameter

Default

OFF Value

ON Value

Dump Delay after shutdown

1

01

00 = OFF

01= 1 hr

Pre-Cool

2

01

00 = OFF

01 = 1.5 min

Dump Interval

3

00

00 = OFF

01,02,03,04,05,06 =
1, 2, 4, 8, 12,24 hrs

Sump fill before Pre-fill

4

01

00= OFF

01 = 1.5 min

Appliance Class

Code

Touch Pad Wall Control

tP

Heater

H

Evaporative A/C

E

Refrigerative A/C

C

Combined Heater - Cooler

HC

Diagnostic Mode

Installer

Maintenance

Parameter

Fill Valve

1

Fill Valve & Pump

2

Fan Speed

Installer

Maintenance

Parameter

Default

Value

Range

Low Fan Speed

1

92

40 – FF

High Fan Speed

2

FF

FF – 9b