Setup & Commissioning

TEK600 Series Control

Page 23

Setting the Fan Speed

To enter into the installer maintenance to adjust minimum and

maximum fan speeds; the following steps must be followed.

STEP 1

Ensure the control is in the OFF mode.

STEP 2

A series of unseen icons must be pressed

1. Press and hold the ZONE 4 icon allowing for a

BUZZ followed by a BEEP.

2. In quick succession press the unseen SETUP

icons ENTER, REVIEW & CLOCK.

3. If successfully executed the clock LEDs will

display tP:01.

4. If unsuccessful repeat 1 and 2 of STEP 2.

STEP 3

Using the

select the LED display changed

to E:_ _.

STEP 4

Press ENTER. The display will now change to 1:01.

STEP 5

Using the

select the parameter to be

changed. Press ENTER.

STEP 6

Using the

change the value as per table

below. Press ENTER to check the revised setting.

STEP 7

To change the other fan speed parameter repeat Step 4 – 7.

STEP 8

Press FINISH to exit.

Fan Speed

Installer

Maintenance

Parameter

Default

Value

Range

Low Fan Speed

1

92

40 – FF

High Fan Speed

2

FF

FF – 9b