Touch Pad Control

Setup & Commissioning

TEK600 Series Control

Page 24

Problem Solving

PROBLEM

PROBABLE CAUSE

REMEDY

a

Black – out

a

Wait

b

Tripped Circuit Breaker

b

Reset

c

Blown Fuse

c

Replace

Unit fails to start

d

Electrical Fault

d

Call Climate Technologies
Service Provider

a

Pump Seized

a

Isolate power and then take off
top of pump and try to free it.
Some lubricant may help.

Pump fails to start

b

Pump Burnt Out

b

Call Climate Technologies
Service Provider

a

Float Valve Leaking

a

Check adjustment or replace seal

Water leaking from
overflow

b

Drain from Celdek Pads

b

Normal Operation

a

Loose Delivery Tube

a

Check and tighten

b

Break in tubing

b

Replace as necessary

Water Droplets in air
stream

c

Pump Delivers Excessive Water to
Pads

c

Adjust the Dialflo to reduce the
flow

a

Inadequate Exhaust

a

Provide more open area to
exhaust stale air

Excessive humidity

b

Outside humidity high

b

Turn pump off.

a

Dirty Filters

a

Clean

b

Dry Filters

b

Check water delivery system.
Adjust if necessary.

Inadequate Cooling

c

Dialflo not set correctly

c

Adjust Dialflo so that the pads
have even saturation.

a

Unit located near odor source

a

Remove source

Unpleasant Odor

b New Celdek filter smell

b

Smell will disappear after a period
of operation.

Rapid formation of
white deposits on
pads

High Mineral Content

Bleed off should be set at
maximum. More regular
maintenance may be required.

THIS TROUBLE SHOOTING GUIDE IS A REFERENCE ONLY.

FOR SERVICE OR WARRANTY REQUIREMENTS PLEASE REFER

TO THE LAST PAGE OF THESE INSTRUCTIONS