Echelon OpenLDV User Manual

Page 117

Advertising
background image

OpenLDV Programmer’s Guide

109

Field

Description

Uplink Lookup Key

The uplink lookup key is an ASCII string (105 characters

maximum) passed to the lookup extension component by the RNI

during an uplink session. It is used by the lookup extension to

access the database record for the RNI that requested the uplink

session, so that the lookup extension component can fill in the rest

of the fields into the SCO. For a SmartServer or i.LON 600, the

uplink lookup key uses the following naming convention:

[Hostname].[DNS Suffix]

[Hostname] represents the hostname assigned to the SmartServer

or i.LON 600 during its configuration. [DNS Suffix] is optional,

and represents the DNS suffix or domain name assigned to the

SmartServer or i.LON 600 during its configuration.
For example, if the hostname for an SmartServer or i.LON 600 is

“myiLON” and the DNS suffix is “xyz.com”, the uplink key would

be “myiLON.xyz.com”.
This field is read-only during uplink sessions, and can be

optionally filled in during downlink sessions. You can set the

downlink key to match the uplink key.

Authentication Flag

This Boolean flag specifies whether authentication between the

OpenLDV application and the RNI is enabled for the session. This

field is always set to true for the SmartServer and i.LON 600.

Current Authentication

Key

If the authentication flag is enabled, this field represents the

authentication key to be used for the session. This authentication

key must match the MD5 authentication key supplied to the RNI

during its configuration. Using an MD5 authentication key

prevents the OpenLDV application or the RNI from responding to

unauthorized messages during an xDriver session.
The authentication key must be entered as a 32-character

hexadecimal string representing a 128-bit MD5 key. For example:

0102030405060708090A0B0C0D0E0F10

Setting the authentication key to all 0s causes xDriver to use the

pre-defined, default factory authentication key for the RNI. The

default factory authentication key is not secure.
For more information about how the lookup extension component

handles authentication, see Authentication Key Handling on page

111.