LNS Programmer's Guide

203

Table 9.2 NvMonitorOptions Object

Property Name

Description

Authentication

This property is not used. If the UseBoundUpdates

option for a monitor point is set to True, the monitor

point’s authentication state is determined by the
UseAuthenticationFlag property of the
ConnectDescTemplate specified when the monitor

point was created. Otherwise, the authentication state is

set based on the monitored network variable’s current

authentication state.

GenerateInitialFetch

This property determines whether the values of the

network variable monitor points in the monitor set will

be fetched when the monitor set is enabled (

True

). If this

property is set to

False

, the value of each network

variable monitor point in the set will not be updated

until a network variable update for that point is received

due to an explicit fetch, bound update, or expired poll
interval.

Default Value: False

PollInterval

This property determines the interval to use when

polling the network variables being monitored by this

set.

Default Value: 1000 ms*

*The default value for this property for temporary

monitor sets is set to match the value of the
DsPollInterval property.