Engineered mode, Definition phase – Echelon LNS User Manual

Page 91

Advertising
background image

LNS Programmer's Guide

77

Engineered Mode

In the engineered mode installation scenario, the network installation consists of two

phases:

1. A

definition phase in which the user defines the configuration of the

devices and connections on the network in the LNS database without

physically modifying the network.

2. A

commissioning phase in which the application loads the network

configuration created during the definition phase from the LNS database
into the physical devices on the network. Application images may also be

loaded during this phase, and some configuration properties may be

adjusted based on testing in order to properly calibrate the system.

Definition Phase

In the definition phase, the network configuration is defined off-site and loaded into the

LNS database, without modifying the physical network. The LNS application defines the

user interface that is used to enter the information. The interface can be anything from a
simple keypad, to a graphic display. The amount of information that the user must enter

is under the control of the application. In the most general case, the user could enter all

the information related to the network, including what devices will be installed on the
network, and how they will be connected. Alternatively, the application could automate

certain parts of the definition process. For example, the user may only need to pick a

configuration from a list of options, or the user may only need to enter device
configuration information while the tool automates connections.

The steps you need to follow to accomplish the tasks involved in the definition phase are

shown in figure 5.2. They are described in more detail in the section following figure 5.2.

Advertising