End view, Side view, 4 connecting the mx52 c – ENMET MX-52 User Manual

Page 12: Figure 7: channel board

Advertising
background image

ENMET Corporation

MX52 C

ONTROL

8

4.4 Connecting the MX52 C

ONTROL

to External Devices

4.4.1 Alarm Relays

The 16 channels of the

MX52 C

ONTROL

unit are each equipped with two relays that can be used to control external

devices such as sirens, solenoid valves, extractors, telephone callers, etc… Auxiliary alarms should be powered from
an independent power source separate from instrument power to avoid alarm failure due to controller malfunction.
An example of connection is given in Figure 8

F

OR EACH CHANNEL

:

The following relays are available (see Figure 7 and 12):

A relay associated with the triggering of alarm 1.

A relay associated with the triggering of alarm 2.

Use of open or closed contacts selected with a jumper (see Figure 7).

Use of positive or negative safety selected by programming (see the CHANNEL programming menu).

Contact outputs on the back of the two channel PCB (see Figure 12).

F

OR

S

YSTEM

R

ELAY

:

A relay associated with the triggering of alarm 3.

A relay associated with the triggering of a system fault.

Figure 7: Channel Board

Output connector

Odd-numbered channel
See End view, below

Output connector

Even-numbered channel
See End View, below

Signal Fuse

Odd-numbered channel

Signal Fuse

Even-numbered channel

Line Fuse

Even-numbered channel

Line Fuse

Odd-numbered channel

Even-numbered channel
Jumpers

Open/closed contacts
Factory set NC

Odd-numbered channel
Jumpers

Open/closed

contacts

Factory set NC

Potentiometers

Odd-numbered channel

Potentiometers

Even-numbered channel

Relay Al1

odd channel

Relay Al2

odd channel

Relay Al1

even channel

Relay Al2

even channel

C1
C2
C3

+

RL

1

RL

2

C1
C2
C3

+

RL

1

RL

2

4-20mA

4-20mA

Output connector

Odd-numbered Channels

Output connector

Even-numbered Channels

Relay Alarm 1

Relay Alarm 2

Relay Alarm 1

Relay Alarm 2

End View

End View

End View

End View

Signal Fuse

Even-numbered channel

Signal Fuse

Even-numbered channel

Side View

Advertising