ENMET MX-52 User Manual

Page 37

Advertising
background image

MX52 C

ONTROL

ENMET Corporation

33

Continued from previous page

An LED does not light up even

though the corresponding threshold

is exceeded and the buzzer and relay

are actuated.

Faulty LED.

Perform a general test on the LEDs

by pressing the TEST switch on

the keypad (Figure 10) and, if the

LED still does not light up, the

programming must be modified by

using the “Unit programming”

menu (buzzer connected).

An alarm is triggered, the LED lights

up and the relay is actuated but there

is no audio alarm.

The buzzer switch is not correctly

positioned.

Position the buzzer switch correctly

(item F, Figure 10).

The buzzer is not programmed as “in

service”.

If the audio alarm is wanted, the

programming must be modified by

using the “unit programming” menu

(buzzer connected?).

The audio alarm stops after 30 s

although alarms are still actuated.

The buzzer is programmed to operate

for 30 seconds only.

If the buzzer is to be sounded as

long as the alarms are actuated, the

programming must be modified by

using the “Unit programming

menu” (continuous buzzer?).

An alarm is triggered but the

auxiliary devices are not actuated.

The relays are faulty.

Short-circuit or open the relay

contact (as applicable) on the MX52

terminal block (Figure 12) and, if

the auxiliary devices operate

normally, the corresponding

channel board must be repaired by

an approved technician.

Faulty electrical connections.

Short-circuit or open the relay

contact (as applicable) on the MX52

terminal block (Figure 12) and, if

the auxiliary devices still do not

work, the connections must be

checked on the MX52 connector

and on the auxiliary devices.

Remote acknowledgement is

impossible.

Faulty electric connections.

Check the connections on the MX52

connector (item B, Figure 9) and on

the pushbutton switch.

The pushbutton switch is faulty.

Replace the pushbutton switch.