Heath Consultants Odorator User Manual

Page 14

Advertising
background image

O

peration

5

Periodic Test:

1. Every thirty (30) days the ODORATOR should be operated with the

power switch on and while not hooked up to a gas supply.

2. Wait about 30 seconds and then position the nose about 3/4 inch (20

mm) above the exhaust port and sniff the exhaust.

3. If no odor is detected, turn the ODORATOR “OFF”. The ODORATOR

has not absorbed the odorant and is usable.

4. If an odor is detected, turn the ODORATOR “OFF” and send it to the

nearest Heath Repair Center (Regional Office) listed on page 19. The

odor is an indication that the ODORATOR has absorbed the odorant

and must have its internal tubing replaced and gas flow components

cleaned.

The forms on pages 8 and 9 are provided to document the Periodic

Tests and are as a courtesy only. Company procedures will define how

records are kept and in what format.

Calibration:

For regulatory compliance, instrument calibration and maintenance

a factory calibration is recommended every 12-15 months from the

date of the previous factory calibration. Only Heath factory or fac-

tory trained personnel should perform ODORATOR calibration. Factory

recognized labels and seals maintain warranty.

Refer to page 19 for Heath repair and calibration centers.